V/F Current Limitation [26] - WEG CFW-11 Programming Manual

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

The factory setting of P0144 (8.0 %) is adequate for standard motors with rated frequency of 60 Hz. When using
a motor with rated frequency (adjusted in P0403) different from 60 Hz, the default value for P0144 may become
inadequate, being able to cause difficulties in the motor starting. A good approximation for the setting of P0144 is
given by the formula:
3
x P0142
P0144 =
P0403
If it is necessary to increase the starting torque, increase gradually the value of P0144.
Output
Voltage
100 %
P0142
P0143
P0144

9.3 V/F CURRENT LIMITATION [26]

P0135 – Maximum Output Current
Adjustable
0.2 to 2xI
Range:
Properties:
V/f and VVW
Access groups
01 PARAMETER GROUPS
via HMI:
P0344 – Current Limitation Configuration
Adjustable
0 = Hold -FL ON
Range:
1 = Decel. -FL ON
2 = Hold -FL OFF
3 = Decel. -FL OFF
Properties:
V/f, CFG and VVW
Access groups
01 PARAMETER GROUPS
via HMI:
Line rated voltage
0.1 Hz
3 Hz
P0146
Figure 9.8 - V/f curve in function of P0142 to P0146
nom-HD
26 V/f Current Limit
26 V/f Current Limit
Scalar Control (V/f)
P0202 = 2
Speed/Frequency
P0145
P0134
Factory
Setting:
Factory
Setting:
1.5xI
nom-HD
3
9
9-7