Vector Control
P0172 – Maximum "-" Torque Current at Maximum Speed
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
Torque current limitation in function of the speed:
This function stays inactive when the contents of P0171/P0172 are higher or equal to the contents of P0169/P0170.
P0171 and P0172 do also act during optimal braking limiting the maximum output current.
P0173 – Maximum Torque Curve Type
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
It defines how the actuation of the torque limitation curve will be at the field weakening region. Refer to the
11.5 on page
11-30.

11.8.7 DC Link Regulator [96]

11
For the deceleration of high inertia loads with short deceleration times, the CFW-11 has available the DC Link
Regulation function, which avoids the tripping of the inverter by overvoltage in the DC link (F022).
11-30
0.0 to 350.0 %
Vector
01 PARAMETER GROUPS
29 Vector Control
95 Torque Curr.Limit
Torque current limitation
P0170/P0169
P0172/P0171
Synchronous speed
Figure 11.5 - Torque limitation actuation curve at maximum speed
0 = Ramp
1 = Step
Vector
01 PARAMETER GROUPS
29 Vector Control
95 Torque Curr.Limit
P0173 = 0
P0173 = 1
P0134
P0190
x
P0400
Factory
125.0 %
Setting: