Multispeed [36] - WEG CFW-11 Programming Manual

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

12.4 MULTISPEED [36]

The MULTISPEED function is used when one wishes to have up to 8 predefined fixed speeds, which are commanded
through the digital inputs (DI4, DI5 and DI6).
P0124 – Multispeed Reference 1
Adjustable
0 to 18000 rpm
Range:
P0125 – Multispeed Reference 2
Adjustable
0 to 18000 rpm
Range:
P0126 – Multispeed Reference 3
Adjustable
0 to 18000 rpm
Range:
P0127 – Multispeed Reference 4
Adjustable
0 to 18000 rpm
Range:
P0128 – Multispeed Reference 5
Adjustable
0 to 18000 rpm
Range:
P0129 – Multispeed Reference 6
Adjustable
0 to 18000 rpm
Range:
P0130 – Multispeed Reference 7
Adjustable
0 to 18000 rpm
Range:
P0131 – Multispeed Reference 8
Adjustable
0 to 18000 rpm
Range:
Properties:
Access groups
01 PARAMETER GROUPS
via HMI:
36 Multispeed
Functions Common to All the Control Modes
Factory
90 rpm
Setting:
(75 rpm)
Factory
300 rpm
Setting:
(250 rpm)
Factory
600 rpm
Setting:
(500 rpm)
Factory
900 rpm
Setting:
(750 rpm)
Factory
1200 rpm
Setting:
(1000 rpm)
Factory
1500 rpm
Setting:
(1250 rpm)
Factory
1800 rpm
Setting:
(1500 rpm)
Factory
1650 rpm
Setting:
(1375 rpm)
12-7
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents