WEG CFW-11 Programming Manual page 42

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Quick Parameter Reference, Faults and Alarms
0
Fault/Alarm
F183
IGBT Overload +
Temperature
F185
(8)
Pre-charge Contac Fault
F186
(9)
Sensor 1 Temperature Fault
F187
(9)
Sensor 2 Temperature Fault
F188
(9)
Sensor 3 Temperature Fault
F189
(9)
Sensor 4 Temperature Fault
F190
(9)
Sensor 5 Temperature Fault
A191
(9)
Sensor 1 Temperature
Alarm
A192
(9)
Sensor 2 Temperature
Alarm
A193
(9)
Sensor 3 Temperature
Alarm
A194
(9)
Sensor 4 Temperature
Alarm
A195
(9)
Sensor 5 Temperature
Alarm
A196
(9)
Sensor 1 Cable Alarm
A197
(9)
Sensor 2 Cable Alarm
A198
(9)
Sensor 3 Cable Alarm
A199
(9)
Sensor 4 Cable Alarm
A200
(9)
Sensor 5 Cable Alarm
F228
Serial Communication
Timeout
F229
Anybus Offline
F230
Anybus Access Error
F233
CAN Bus Power Failure
F234
Bus Off
F235
CANopen Communication
Error
F236
Master Idle
F237
DeviceNet Connect
Timeout
(*) Temperature > 40 ºC or 45 ºC, depending on the model. Refer to the section 3.1 - Installation Environment, of the CFW-11M user's manual.
0-34
Description
Overtemperature related to the IGBTs overload
protection.
It indicates fault at the pre-charge Contactor.
It indicates a temperature fault at the sensor 1.
It indicates a temperature fault at the sensor 2.
It indicates a temperature fault at the sensor 3.
It indicates a temperature fault at the sensor 4.
It indicates a temperature fault at the sensor 5.
It indicates a temperature alarm at the sensor 1.
It indicates a temperature alarm at the sensor 2.
It indicates a temperature alarm at the sensor 3.
It indicates a temperature alarm at the sensor 4.
It indicates a temperature alarm at the sensor 5.
Sensor 1 cable alarm.
Sensor 2 cable alarm.
Sensor 3 cable alarm.
Sensor 4 cable alarm.
Sensor 5 cable alarm.
Refer to the RS-232 / RS-485 Serial communication manual.
Refer to the Anybus-CC communication manual.
Refer to the CANopen communication manual and/or the DeviceNet communication manual.
Refer to the CANopen communication manual.
Refer to the DeviceNet communication manual.
Possible Causes
Surrounding air temperature too high.
Operation with frequencies < 10 Hz under overload.
Pre-charge contactor defect.
Open command fuse.
Phase loss in the input L1/R or L2/S.
P0355 = 1 (Incorrect setting for models frame E or frame
H supplied by the DC link. For those models, the setting
should be P0355 = 0.
Motor high temperature.
Motor high temperature.
A problem in the wiring connecting the sensor to the IOE
01 (02 or 03).
Shorted temperature sensor.