P0044 – kWh Counter
Adjustable
0 to 65535 kWh
Range:
Properties:
RO
Access groups
09 READ ONLY PARAMETERS
via HMI:
Description:
It indicates the energy consumed by the motor.
It indicates up to 65535 kWh, and then it gets back to zero.
By setting P0204 = 4, the value of the parameter P0044 is reset to zero.
This value is kept even when power is removed from the inverter. The content of P0044 is recorded on the EEPROM
when the condition of undervoltage on the DC Link is detected.
NOTE!
The value indicated in this parameter is calculated indirectly, and must not be used to measure the
energy consumption.
P0045 – Fan Enabled Time
Adjustable
0 to 65535 h
Range:
Properties:
RO
Access groups
09 READ ONLY PARAMETERS
via HMI:
Description:
It indicates the total number of hours that the heatsink fan remained enabled.
It indicates up to 65535 hours, and then it gets back to zero.
By setting P0204 = 2, the value of the parameter P0045 is reset to zero.
This value is kept even when power is removed from the inverter. The content of P0045 is recorded on the EEPROM
when the condition of undervoltage on the DC Link is detected.
P0048 – Present Alarm
P0049 – Present Fault
Adjustable
0 to 999
Range:
Properties:
RO
Access groups
09 READ ONLY PARAMETERS
via HMI:
Read Only Parameters [09]
Factory
Setting:
Factory
Setting:
Factory
Setting:
16
16-9