Self-Tuning [05] And [94] - WEG CFW-11 Programming Manual

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

P0183 – Current in the I/f Mode
Adjustable
0 to 9
Range:
Properties:
Sless
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
It defines the current to be applied to the motor when the inverter is operating in the I/f mode, i.e., with the motor
speed below the value defined by P0182.

11.8.5 Self-Tuning [05] and [94]

In that group are the parameters that are related to the motor and can be estimated by the inverter during the
self-tuning routine.
P0408 – Run Self-Tuning
Adjustable
0 = No
Range:
1 = No Rotation
2 = Run for I
3 = Run for T
4 = Estimate T
Properties:
CFG, Vector and VVW
Access groups
01 PARAMETER GROUPS
via HMI:
NOTE!
The commands via communication network, SoftPLC and PLC11 remain inactive during the self-tuning.
29 Vector Control
93 I/F Control
Table 11.5 - Current applied in the I/f mode
Current in the I/f mode as a percentage of P0410 (I
P0183
0
1
2
3
4
5
6
7
8
9
m
m
m
29 Vector Control
94 Self-tuning
)
m
100 %
120 %
140 %
160 %
180 %
200 %
220 %
240 %
260 %
280 %
05 SELF-TUNING
or
Vector Control
Factory
1
Setting:
Factory
0
Setting:
11-23
11