WEG CFW-11 Programming Manual page 235

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Description:
This parameter allows disabling the actuation of F185 fault – Fault in the preload contactor.
If P0355 = 0, the Fault in the preload contactor will remain deactivated. F185 fault will not be generated.
When the inverter is a frame size E with DC power supply it's necessary to adjust P0355 = 0.
P0356 – Dead Time Compensation
Adjustable
0 = Off
Range:
1 = On
Properties:
CFG
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
This parameter must be kept always in 1 (On). Only in special maintenance cases the value 0 (Off) can be used.
P0357 – Line Phase Loss Time
Adjustable
0 to 60 s
Range:
Properties:
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
It configures the time for the line phase loss indication (F006).
If P0357 = 0, the function remains disabled.
NOTE!
The function Phase Loss will be automatically disabled when detected some of the models: CFW11
0010 S 2024, CFW11 0006 S 2024FA or CFW11 0007 S 2024 FA.
If the inverter has single-phase power supply, it is necessary to adjust P0357 = 0 to disable the fault
F006.
45 Protections
45 Protections
Faults and Alarms
Factory
1
Setting:
Factory
3 s
Setting:
15-15