Digital and Analog Inputs and Outputs
Description:
It specifies the value in rpm, ± 1 % of the motor rated speed (hysteresis), below which the actual speed will be
considered null for the Zero Speed Disable function.
This parameter is also used by the functions of the digital and relay outputs, and by the PID regulator. The hysteresis is
± 0.22 % of the motor rated speed.
P0292 – N = N* Band
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
It is used in the N = N* function of the digital and relay outputs.
P0293 – Tx Torque
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
It is used in the Torque > Tx and Torque < Tx functions of the digital and relay outputs.
In those functions the motor torque indicated in P0009 is compared with the value adjusted in P0293.
The setting of this parameter is expressed as a percentage of the motor rated current (P0401 = 100 %).
P0294 – Hx Time
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
It is used in the Enabled Hours > Hx function of the digital and relay outputs.
13
13-28
0 to 18000 rpm
07 I/O CONFIGURATION
41 Digital Outputs
0 to 200 %
07 I/O CONFIGURATION
41 Digital Outputs
0 to 6553 h
07 I/O CONFIGURATION
41 Digital Outputs
Factory
Setting:
or
01 PARAMETER GROUPS
41 Digital Outputs
Factory
Setting:
or
01 PARAMETER GROUPS
41 Digital Outputs
Factory
Setting:
or
01 PARAMETER GROUPS
41 Digital Outputs
18 rpm
(15 rpm)
100 %
4320 h