Parameter
Function
P0251
AO1 Function
P0252
AO1 Gain
P0253
AO1 Signal Type
P0254
AO2 Function
P0255
AO2 Gain
P0256
AO2 Signal Type
Quick Parameter Reference, Faults and Alarms
Adjustable Range
Factory Setting
0 = Speed Ref.
1 = Total Ref.
2 = Real Speed
3 = Torque Cur.Ref
4 = Torque Current
5 = Output Current
6 = Process Var.
7 = Active Current
8 = Output Power
9 = PID Setpoint
10 = Torque Cur.> 0
11 = Motor Torque
12 = SoftPLC
13 = PTC
14 = Not Used
15 = Not Used
16 = Motor Ixt
17 = Encoder Speed
18 = P0696 Value
19 = P0697 Value
20 = P0698 Value
21 = P0699 Value
22 = PLC11
23 = Id* Current
0.000 to 9.999
0 = 0 to 10 V/20 mA
1 = 4 to 20 mA
2 = 10 V/20 mA to 0
3 = 20 to 4 mA
See options in P0251
0.000 to 9.999
See options in P0253
User
Properties
Setting
2
-
1.000
-
0
CFG
5
-
1.000
-
0
CFG
0
Groups
Pag.
39
13-8
39
13-9
39
13-11
39
13-8
39
13-9
39
13-11
0-9