Faults and Alarms
Description:
These parameters allow selecting the type of desired action, temperature fault, temperature alarm or broken cable
alarm. The rupture of the cable that connects the sensor to the IOE-0x module may cause any of those actions,
depending on the selected option.
The
Table 15.8 on page 15-20
These parameters will be visible on the HMI only when the IOE-01, IOE-02 or IOE-03 optional module is connected
into the slot 1 (XC41 connector). Refer to the
P0374/P0377/P0380/P0383/P0386
0 = Inactive
1 = Temperature fault/Temperature alarm/
Cable alarm
2 = Temperature fault/Cable alarm
3 = Temperature alarm/Cable alarm
4 = Temperature fault/Temperature alarm
5 = Temperature fault
6 = Temperature alarm
7 = Cable alarm
(*) Once a fault is generated, the inverter will be disabled.
Temperature alarm or broken cable alarm will only affect the HMI. The inverter status (P0006) will not be changed.

15.4.1 PTC Type Temperature Sensor

The next parameters will be shown on the HMI when the IOE-01 module is connected into the slot 1 (XC41
connector). Refer to the
P0373 - PTC 1 Sensor Type
P0376 - PTC 2 Sensor Type
P0379 - PTC 3 Sensor Type
P0382 - PTC 4 Sensor Type
P0385 - PTC 5 Sensor Type
Adjustable
Range:
Properties:
Access groups
via HMI:
15
Description:
These allow selecting the type of used PTC sensor: single or triple.
15-20
details the actuation of each available option.
Figure 3.1 on page
Table 15.8 - Available options at parameters P0374/P0377/P0380/P0383/P0386
The temperature protection is disabled
No faults or alarms will be generated
The inverter will generate the fault (F186/F187/F188/F189/F190)
temperature alarm (A191/A192/A193/A194/A195), or the broken cable alarm (A196/
A197/A198/A199/A200)
The inverter will generate the fault (F186/F187/F188/F189/F190)
broken cable alarm (A196/A197/A198/A199/A200)
The inverter will exhibit the temperature alarm (A191/A192/A193/A194/A195), or the
broken cable alarm (A196/A197/A198/A199/A200)
The inverter will generate the fault (F186/F187/F188/F189/F190)
temperature alarm (A191/A192/A193/A194/A195)
The inverter will generate the fault (F186/F187/F188/F189/F190)
The inverter will exhibit the temperature alarm (A191/A192/A193/A194/A195)
The inverter will exhibit the broken cable alarm (A196/A197/A198/A199/A200)
Figure 3.1 on page
0 = Single PTC
1 = Triple PTC
CFG
01 PARAMETER GROUPS
45 Protections
3-2.
Action
3-2.
, will exhibit the
(*)
or will exhibit the
(*)
or will exhibit the
(*)
(*)
Factory
1
Setting: