Vector Control
Description:
This parameter defines the DC link voltage regulation level during the braking. During the braking, the time of the
deceleration ramp is automatically extended, thus avoiding an overvoltage fault (F022). The setting of the DC link
regulation can be done in two manners:
1. With loss (optimal break) – set P0184 = 0.
1.1 - P0404 < 20 (60 hp): In this way the current flux is modulated in a way to increase the losses of the
motor, increasing the break torque. A better operation can be obtained with motors of smaller efficiency
(small motors).
1.2 - P0404>20 (60 hp): the current flux will be increased up to the maximum value defined on P0169
or P0170, as the speed is reduced. The break torque in the weakness field area is small.
2. Without losses – set P0184 = 1. Activates only the DC link voltage regulation.
NOTE!
The factory setting for P0185 is adjusted at the maximum, which disables the DC link voltage
regulation. In order to activate it, set P0185 according to the
Inverter
V
nom
P0296
P0185
P0186 – DC Link Voltage Regulation Proportional Gain
Adjustable
Range:
P0187 – DC Link Voltage Regulation Integral Gain
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
These parameters adjust the DC link voltage regulator gain.
Normally the factory settings are adequate for the majority of the applications, not being necessary to adjust them.
11
11-32
Table 11.9 - DC link voltage regulation recommended levels
200 ...
400 /
380 V
240 V
415 V
0
1
2
375 V
618 V
675 V
0.0 to 63.9
0.000 to 9.999
PM and Vector
01 PARAMETER GROUPS
29 Vector Control
96 DC Link Regulator
Table 11.9 on page
440 /
500 /
550 /
480 V
460 V
525 V
575 V
3
4
5
748 V
780 V
893 V
972 V
11-32.
660 /
600 V
690 V
6
7
8
972 V
1174 V
Factory
18.0
Setting:
Factory
0.002
Setting: