Quick Parameter Reference, Faults and Alarms
Models where they can occur:
0
(1) All the models from frame size A to G.
(2) CFW110086T2, CFW110105T2, CFW110045T4, CFW110058T4, CFW110070T4 and CFW110088T4.
(3) All the models of frame sizes D and E.
(4) All the models of frame sizes A, B and C.
(5) With a Profibus DB module connected into the slot 3 (XC43).
(6) CFW110370T4, CFW110477T4, CFW11XXXXT6 in frame size F and all the frame size G models.
(7) All the models of the frame size G.
(8) All the models of the frame size E.
(9) With IOE-01 (02 or 03) modules connected into the slot 1 (XC41).
(10) All the models of the CFW-11M.
(11) All the models with a SoftPLC applicative.
(12) All the models of frame sizes F and G.
(13) All the models of frame sizes D, E, F, G and CFW-11M.
(14) Long motor cables (with more than 100 meters) (328.08 ft) will have a high leakage capacitance to the
ground. The circulation of leakage currents through these capacitances may activate the ground fault
protection after the inverter is enabled, and consequently, the occurrence of fault F074.
(15) All the models of frame H.
NOTE!
The range from P0750 to P0799 is destined to the SoftPLC applicative user faults and alarms.
0-40