Back" (t4) level, defined at the parameter P0323. The motor will reaccelerate, following the adjusted ramp, from the
actual speed value to the value defined by the speed reference (P0001) (refer to the
U
d
Nominal
Return (P0323)
Loss (P0321)
Ride-Through (P0322)
Undervoltage (75 %)
Figure 12.8 - Ride-Through function actuation in vector mode
t0 – Line loss.
t1 – Line loss detection.
t2 – Undervoltage actuation (F021 without Ride-Through).
t3 – Line return.
t4 – Line return detection.
t5 – Undervoltage actuation (F021 with Ride-Through).
If the line voltage produces an U
may occur, the values of P0321, P0322 and P0323 must be readjusted.
NOTE!
When one of the functions, Ride-Through or Flying Start, is activated, the parameter P0357 (Line
Phase Loss Time) is ignored, regardless of the adjusted time.
NOTE!
Cautions with the application:
All the drive system components must be dimensioned to withstand the application transitory
conditions.
NOTE!
The Ride-Through function activation occurs when the power supply voltage is lower than the value
(P0321/1.35).
U
=VAC x 1.35
d
Functions Common to All the Control Modes
t0 t1
t2
voltage between the values adjusted in P0322 and P0323, the fault F0150
d
Figure 12.8 on page
F021
t
(t)
t3
t4 t5