WEG CFW-11 Programming Manual page 155

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Seq.
Action/Result
- If necessary, change
the content of P0296
according to the used line
voltage. Therefore press
"Select". This change will
10
affect P0151, P0153,
P0185, P0190, P0321,
P0322, P0323 and
P0400.
- If necessary, change
the content of P0298
according to the inverter
application. Therefore
press "Select". This
change may affect P0156,
P0157, P0158, P0169,
11
P0170, P0401 and
P0404. The actuation
time and level of the
IGBTs overload protection
will also be affected.
- If necessary adjust
the content of P0398
according to the motor
service factor. Therefore
press "Select". This change
12
will affect the current
value and the time for the
actuation of the motor
overload function.
- If necessary, change
the content of P0400
according to the rated
motor voltage. Therefore
13
press "Select". This change
will affect P0190.
- If necessary, change
the content of P0401
according to the rated
motor current. Therefore
14
press "Select". This change
will affect P0156, P0157
and P0158.
Display Indication
Config
0rpm
LOC
Type of Control
P0202: Sensorless
Line Rated Voltage
P0296: 440 - 460 V
Reset
13:48
Select
Config
0rpm
LOC
Line Rated Voltage
P0296: 440 - 460 V
Application
P0298: Normal Duty
Reset
13:48
Select
Config
LOC
0rpm
Application
P0298: Normal Duty
Motor Service Factor
P0398:
1.15
Reset
13:48
Select
Config
0rpm
LOC
Motor Service Factor
P0398:
1.15
Motor Rated Voltage
P0400:
440V
Reset
13:48
Select
Config
0rpm
LOC
Motor Rated Voltage
P0400:
440V
Motor Rated Current
P0401:
13.5 A
Reset
13:48
Select
Seq.
Action/Result
- If necessary, change
the content of P0402
according to the rated
motor speed. Therefore
press "Select". This change
15
may affect P0122 to
P0131, P0133, P0134,
P0182, P0208, P0288
and P0289.
- If necessary, change
the content of P0403
according to the rated
16
motor frequency. Therefore
press "Select".
- If necessary, change
the content of P0404
according to the rated
17
motor power. Therefore
press "Select".
- This parameter will only be
visible if the encoder board
ENC1, ENC2 or PLC11
module is connected to the
inverter.
- If there is an encoder
18
connected to the motor,
change P0405 according
to its number of pulses per
revolution. Therefore press
"Select".
- If necessary, change
the content of P0406
according to the type
of motor ventilation.
Therefore press "Select".
19
This change will affect
P0156, P0157, P0158,
P0399 and P0407.
Vector Control
Display Indication
Config
0rpm
LOC
Motor Rated Current
P0401:
13.5A
Motor Rated Speed
P0402= 1750rpm
Reset
13:48
Select
Config
0rpm
LOC
Motor Rated Speed
P0402:
1750 rpm
Motor Rated Frequency
P0403: 60Hz
Reset
13:48
Select
Config
0rpm
LOC
Motor Rated Frequency
P0403:
60Hz
Motor Rated Power
P0404:
7.5hp
Reset
13:48
Select
Config
0rpm
LOC
Motor Rated Power
P0404: 7.5hp
Encoder Pulses Number
P0405: 1024 ppr
Reset
13:48
Select
Config
0rpm
LOC
Encoder Pulses Number
P0405: 1024 ppr
Motor Ventilation
P0406: Self-Vent.
Reset
13:48
Select
11-37
11

Hide quick links: