NOTE!
 Every time that P0408 = 1 or 2:
The parameter P0413 (Mechanic time constant – Tm) will be adjusted to a value close to the motor
mechanic time constant. Therefore, the motor rotor inertia (table data valid for WEG motors), the
inverter rated voltage and current are taken into consideration.
 Vector mode with encoder (P0202 = 4):
When using P0408 = 2 (Run for I
load to the motor and set P0408 = 4 (Estimate T
case P0413 will also consider the driven load.
 VVW mode – Voltage Vector WEG (P0202 = 5):
In the VVW control self-tuning routine only the value of the stator resistance (P0409) will be obtained.
Therefore, the self-tuning will always be performed without rotating the motor.
 Better self-tuning results are obtained with the motor warm.
P0409 – Motor Stator Resistance (Rs)
Adjustable
0.000 to 9.999 ohm
Range:
Properties:
CFG, Vector and VVW
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
Estimated value and automatically adjusted by the self-tuning
parameter can also be obtained on the motor data sheet
P0412 Based on the Motor Data Sheet on page
NOTE!
The P0409 setting determines the value of the current regulator integral gain P0168. The parameter
P0168 is recalculated every time the content of P0409 is modified via keypad (HMI).
P0410 – Motor Magnetizing Current (I
Adjustable
0 to 1.25 x I
Range:
Properties:
V/f, VVW and Vector
Access groups
01 PARAMETER GROUPS
via HMI:
), one must, after finishing the self-tuning routine, couple the
m
29 Vector Control
94 Self-tuning
11-15).
)
m
nom-ND
29 Vector Control
94 Self-tuning
) in order to estimate the value of P0413. In this
m
05 SELF-TUNING
or
(Section 11.3 SELF-TUNING on page
(Item 11.7.1 Adjustment of the Parameters P0409 to
05 SELF-TUNING
or
Vector Control
Factory
0.000 ohm
Setting:
11-5). This
Factory
I
nom-ND
Setting:
11-25
11