WEG CFW-11 Programming Manual page 268

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Trace Function [52]
Description:
It defines the value for comparison with the variable selected in P0550.
The full range of the variables selectable as trigger is presented in the next table.
This parameter has no effect when P0552 = "Alarm", "Fault" or "DIx".
P0552 – Trigger Condition for Trace
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
It defines the condition for starting the signal acquisition. The
For P0552=6 ("DIx" option), it is necessary to select the option "Trace Function" at one of the parameters from P0263
19
to P0270. For more details, refer to the
Notes:
- If P0552 = 6 and no DI is configured for "Trace Function", the trigger will not occur.
- If P0552 = 6 and several DIs were configured for "Trace Function", only one has to be active for the trigger
occurrence.
19-2
Table 19.1 - Full scale of the variables selectable as trigger
Variable
Speed Reference
Motor Speed
Motor Current
DC Link Voltage
Motor Frequency
Motor Voltage
Motor Torque
Process Variable
PID Setpoint
AI1
AI2
AI3
AI4
0: P0550* = P0551
1: P0550* <> P0551
2: P0550* > P0551
3: P0550* < P0551
4: Alarm
5: Fault
6: DIx
01 PARAMETER GROUPS
52 Trace Function
Table 19.2 - Parameter P0552 option description
P0552 Options
P0550* = P0551
The variable selected in P0550 is equal to the value adjusted in P0551
P0550* ≠ P0551
The variable selected in P0550 is different from the value adjusted in P0551
P0550* > P0551
The variable selected in P0550 is bigger than the value adjusted in P0551
P0550* < P0551
The variable selected in P0550 is smaller than the value adjusted in P0551
Alarm
Fault
DIx
Item 13.1.3 Digital Inputs [40] on page
Full Scale
100 % = P0134
100 % = P0134
200 % = 2.0 x I
nomHD
100 % = Max. Lim. P0151
340 % = 3.4 x P0403
100 % =1.0 x P0400
200 % = 2.0 x I
nom Motor
100 % = 1.0 x P0528
100 % = 1.0 x P0528
100 % = 10 V/20 mA
100 % = 10 V/20 mA
100 % = 10 V/20 mA
100 % = 10 V/20 mA
Table 19.2 on page 19-2
Description
Inverter with an active alarm
Inverter in fault state
Digital input (selected via P0263 – P0270)
Factory
5
Setting:
details the available options.
13-12.