P0398 – Motor Service Factor
Adjustable
1.00 to 1.50
Range:
Properties:
CFG
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
It is the continuous overload capability, i.e., a reserve of power that gives the motor the capability to withstand
working in adverse conditions.
Set it according to the value informed on the motor nameplate.
It affects the motor overload protection.
P0399 – Motor Rated Efficiency
Refer to the
Section 10.2 MOTOR DATA [43] on page
P0400 – Motor Rated Voltage
Adjustable
0 to 690 V
Range:
Properties:
CFG
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
Set it according to the motor nameplate data and to the motor cable wiring in the connection box.
This value cannot be higher than the rated voltage adjusted in P0296 (Line Rated Voltage).
NOTE!
In order to validate a new P0400 setting out of the Oriented Start-up Routine it is necessary to cycle
the power of the inverter.
P0401 – Motor Rated Current
Adjustable
0 to 1.3xI
Range:
Properties:
CFG
Access groups
01 PARAMETER GROUPS
via HMI:
43 Motor Data
10-3, for more details.
43 Motor Data
nom-ND
43 Motor Data
Vector Control
Factory
Setting:
Factory
220 V (P0296 = 0)
Setting:
440 V (P0296 = 1, 2, 3 or 4)
575 V (P0296 = 5 or 6)
690 V (P0296 = 7 or 8)
Factory
Setting:
1.00
1.0xI
nom-ND
11