Settings
Exam
When canceling the transfer
ple 3
of LOG7
When enabling the sending of
Exam
ple 4
send number 10
(Note 1)
For specifying a device for an operand which can specify character constants, store string data with
SSET instruction excluding a double quotation mark.
Mail transmission control relay flag operation
Name
Send cancel relay
Send disable relay
Send request
Send active
Send retry active
Send done
Send failed
Send direction
(Note 1)
The send cancel relay turns OFF when the SMTPc transfer request instruction is executed.
Flag operations
Name
Description
To be set when an item other than "IDx" or "LOGx" or "ALL" is specified for the control target (S1).
(x: 0 to 15)
To be set when an item other than "ENABLE", "DISABLE" or "CANCEL" is specified for the control
content (S2).
SR7
To be set when the slot number [S1] specified with UNITSEL is not 100 (built-in ET-LAN).
SR8
Set when the number of characters for operand specifying character constant exceeds 256.
(ER)
To be set when a mail transmission setting that has not been specified with the mail transmission
setting instruction or the tool software is specified.
To be set when a logging/trace mail setting that has not been specified with the logging/trace mail
setting instruction or the tool software is specified.
CY
Set when the instruction is the initialization of Ethernet. The detail code set in SD29 is "11:
Ethernet initialization active".
(SR9)
(Note 1)
For details of the error codes stored in the system data SD29, refer to
Registers".
WUME-FP7CPUPGR-12
17.27 SMTPcCTL (Mail Transmission Control)
S1
"LOG7"
DT0
DT0
DT1
(Note 1)
DT2
DT3
Transfer enabled
Not change
OFF
Not change
Not change
Not change
Not change
Not change
Not change
Value
4 (No. of characters)
H44(D)
H49(I)
H30(0)
H31(1)
Transfer disabled
Not change
ON
Not change
Not change
Not change
Not change
Not change
Not change
S2
"CANCEL"
DT10
Value
DT10
6 (No. of characters)
DT11
H4E(N)
DT12
H42(B)
DT13
H45(E)
DT14
Transfer canceled
ON
Not change
Not change
Not change
Not change
Not change
Not change
Not change
"20.2 List of System Data
H45(E)
H41(A)
H4C(L)
17-141