CIP message send data format
Value
D
CIP data length
D+1
Service code
D+2
General Status
D+3 onward CIP data
Stores the following three
data items as CIP message
S2: Specify the data format and data size of the data to be acquired.
Specified range: 0 to 504 (000H to 1F8H)
Set value Description
0
Character string
1 to 504
Other than character string
D1: Specify the device that stores the data acquisition starting position.
Update the data equivalent to the number of data acquired after the instruction is completed.
Starting data length size is not included in the starting position.
WUME-FP7CPUPGR-12
17.34 CIPMGET (CIP Message Data Getting)
} CIP receive header
Complex data consisting of short type, double type, and string data type
Value
DT0 0011H
DT1
CIP receive header
DT2
DT3 0001H
data:
1
DT4 02H
AB
1234H
DT5 41H (A)
DT6 34H
DT7 ffH
Specify when acquired data is character strings.
Acquire data equivalent to "Starting device value of S1 + 2".
Specify when acquired data is other than character strings.
Acquire data equivalent to "set value".
Data length
1st data: '1'
(Note): The starting one word of the character string
31H (1)
data is for the character string length.
00H
2nd data: 'AB'
(Note): The starting one word of the character string
42H (B)
data is for the character string length.
3rd data: 1234H
12H
17-169