Automatic additional information: Not add automatically, Specification of attached data: No
Settings
attached file
Exam
S4
"INFO=ADD,ATT=NONE"
ple 2
Automatic additional information: Add automatically, Specification of attached data: No attached
Settings
file
Exam
S4
"INFO=NON,ATT=DATA,DT100,10,HEX1w"
ple 3
Automatic additional information: Not add automatically, Specification of attached data: Specify
device (attached to mail text)
Settings
Device setting, Device division: Global, Device code: DT, Device No.: 100
No. of transferred data: 10 points (10 words), Conversion method: 16-bit HEX
Exam
S4
"INFO=ADD,ATT=DATA,PB100_WR1000,50,US,FILE=PB100_WR1000_50.csv,TOP"
ple 4
Automatic additional information: Add automatically, Specification of attached data: Specify device
Device setting, Device division: Local, PB number: 100, Device code: WR, Device number: 1000
Settings
Number of transferred data: 50 points (50 words), Conversion method: 16-bit unsigned decimal,
Addition of attached file: FIL=PB100_WR1000_50.csv,
Automatic addition position: Automatic additional data is added before the file name.
Exam
S4
"INFO=NON,ATT=FILE,\Folder\FileName.bin"
ple 5
Automatic additional information: Not add automatically, Specification of attached data: specify file
Settings
(\Folder\FileName.bin)
Flag operations
Name
Description
To be set when an out-of-range value is specified for parameters.
To be set when the slot number [S1] specified with UNITSEL is not 100 (built-in ET-LAN).
To be set when setting numbers are not specified in ascending order.
To be set when the same destination group number is specified redundantly.
To be set when executed in an interrupt program.
SR7
To be set when the send request of the mail transmission control relay of a specified setting
SR8
number is 1: Requesting.
(ER)
To be set when the number of characters for an operand that allows specifying a character
constant exceeds its upper limit. The upper limit is 4096 characters for CPU units Ver.4.1 or later,
and Ver.3.4 to Ver.3.x, and 256 characters at maximum for other CPU units.
To be set when a mail sending server that has not been specified with the destination server
setting instruction or the tool software is specified.
To be set when a destination group number that has not been specified with the destination group
setting instruction or the tool software is specified.
CY
Set when the instruction is the initialization of Ethernet. The detail code set in SD29 is "11:
Ethernet initialization active".
(SR9)
(Note 1)
For details of the error codes stored in the system data SD29, refer to
Registers".