Alarms, faults and system messages

8.6 List of alarms and faults

8.6
List of alarms and faults
Overview
A message comprises a letter followed by the relevant number.
The letters have the following meaning:
A . . . .
F . . . .
The expressions have the following meaning:
CU/Power Module/power unit All refer to an Electronic Module.
Important alarms and faults
Number
Cause
F01000
Software fault in CU
F01001
Floating Point Exception
F01015
Software fault in CU
F01018
Power-up aborted more than once
A01028
Configuration error
F01033
Unit switchover: Reference param-
eter value invalid
F01034
Unit switchover: Calculation of the
parameter values after reference
value change unsuccessful
F01040
Parameters must be saved
F01044
Loading of memory data card de-
fective
A01101
Memory card not available
F01105
CU: Insufficient memory
F01122
Frequency at the probe input too
high
F01205
CU: Time slice overflow
F01250
CU hardware fault
F01512
An attempt has been made to es-
tablish a conversion factor for scal-
ing which is not present
332
Alarm code . . . .
Fault code . . . .
For example, replacing a CU, Power Module, or power unit
means replacing an Electronic Module.
Remedy
Replace CU.
Switch CU off and on again.
Upgrade firmware or contact technical support.
1. Switch the module off and on again.
2. After this fault has been output, the module is booted with the factory settings.
3. Recommission the converter.
Explanation: Parameterization on the memory card has been created with
a different type of module (article number, MLFB)
Check the module parameters and recommission if necessary.
Set the value of the reference parameter not equal to 0.0 (p0304, p0305,
p0310, p0596, p2000, p2001, p2002, p2003, r2004).
Select the value of the reference parameter so that the parameters in-
volved can be calculated in the per unit notation (p0304, p0305, p0310,
p0596, p2000, p2001, p2002, p2003, r2004).
Save parameters (p0971).
Switch CU off and on again.
Replace memory card or CU.
Insert a memory card or disable the warning A01101.
Activating message for a memory card that is not inserted
(Page 310)
Reduce number of data records.
Reduce the frequency of the pulses at the probe input.
Contact technical support.
Replace CU.
Create scaling or check transfer value.
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002