Parameters
Parameters of the fault buffer and the fault history
Parameter
r0945[0 ... 63]
r0948[0 ... 63]
r0949[0 ... 63]
p0952
r2109[0 ... 63]
r2130[0 ... 63]
r2131
r2133[0 ... 63]
r2136[0 ... 63]
Extended settings for faults
Parameter
You can change up to 20 different faults into alarms, suppress faults, modify the fault response, or
modify the acknowledgment mode:
p2100[0 ... 19]
p2101[0 ... 19]
p2118[0 ... 19]
p2119[0 ... 19]
p2126[0 ... 19]
p2127[0 ... 19]
For more information about this function, see function diagram 8075 and parameter
description in the List Manual.
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
Description
Fault code
Fault time received in milli-
seconds
Fault value
Fault cases counter
Fault time removed in milli-
seconds
Fault time received in days
Actual fault code
Fault value for float values
Fault time removed in days
Description
Changing fault response,
fault number
Changing the fault reaction,
reaction
Changing message type,
message number
Changing message type,
type
Changing the acknowledg-
ment mode, fault number
Changing the acknowledg-
ment mode
Alarms, faults and system messages
8.5 Faults, fault buffer and fault history
Setting
Displays the numbers of the faults that have occurred.
Displays the system runtime in milliseconds when the
fault occurred.
Displays additional information about the fault that
occurred (as integer number).
Number of fault cases that have occurred since the
last acknowledgment.
With p0952 = 0, you delete the fault buffer and the
fault history.
Factory setting: 0
Displays the system runtime in milliseconds when the
fault was removed.
Displays the system runtime in days when the fault
occurred.
Displays the code of the oldest active fault.
Displays additional information about the fault that
occurred for float values.
Displays the system runtime in days when the fault
was removed.
Setting
Selects the faults for which the fault response should
be changed.
Factory setting: 0
Sets the fault reaction for the selected fault.
0: NONE
1: OFF1
2: OFF2
3: OFF3
5: STOP2
6: Internal armature short-circuit / DC braking
Factory setting: 0
Selects faults or alarms for which the message type
should be changed.
Factory setting: 0
Sets the message type for the selected fault or alarm.
1: Fault
2: Alarm
3: No message
Factory setting: 1
Selects the faults for which the acknowledge mode is
to be changed.
Factory setting: 0
Sets the acknowledgment type for the selected fault:
1: Acknowledgment only using POWER ON
2: Immediate acknowledgment after removing the
fault cause
Factory setting: 1