Advanced commissioning

6.6 Drive control via Ethernet/IP

6.6
Drive control via Ethernet/IP
6.6.1

Configuring communication via Ethernet/IP

Overview
Ethernet/IP is real-time Ethernet, and is mainly used in automation technology.
Function description
To configure the converter's communication via Ethernet/IP, you must set the following
parameters:
Procedure
1. p2030 = 10
2. The following parameters must match your Ethernet configuration:
– p8921 = IP address
– p8922 = default gateway
– p8923 = subnet mask
– p8920 = station name
3. p8925 = 2
4. Select the Ethernet/IP profile:
5. Switch off the converter power supply.
6. Wait until all LEDs on the converter are dark.
7. Switch on the converter power supply again.
You have now configured the converter for communication via Ethernet/IP.
Parameters
Parameter
p2030
p8920
148
SINAMICS profile
ODVA AC/DC drive profile
p8980 = 0
p8980 = 1
Use p0922 to select
p0922 = 1: The converter communicates via telegram 1. Other telegrams are
the appropriate
not possible. If necessary, however, you can extend the telegram 1.
telegram.
Telegrams
If necessary, set the following parameters:
(Page 135)
p8981
p8982
p8983
Description
Fieldbus interface protocol
selection
PN Name of Station
Expanding or freely interconnecting telegrams (Page 145)
Setting
0: No protocol
7: PROFINET
10: Ethernet/IP
The default setting is dependent upon the converter.
Sets the station name for the onboard PROFINET interface.
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
SINAMICS G115D distributed drive