Configuring The Star/Delta Connection Of The Wall-Mounted Converter; Connecting The 24 V Power Supply; Interface Description - X01/X02 - Siemens SINAMICS G115D Operating Instructions Manual

Distributed drive for conveyor technology control
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

4.10.2.2

Configuring the star/delta connection of the wall-mounted converter

The star/delta connection is implemented inside the terminal box of the motor. You can
configure the connection according to the circuit diagram of the motor.
Star connection
4.11

Connecting the 24 V power supply

Electric shock due to unsuitable power supply
When equipment is connected to an unsuitable power supply, exposed components may
carry a hazardous voltage that might result in serious injury or death.
• Only use power supplies that provide SELV (Safety Extra Low Voltage) or PELV-
4.11.1

Interface description - X01/X02

Connector variant
One of the two types of connectors (7/8" and M12 L-coding) is provided depending on the
variant that has been ordered.
7/8" connector
X01 - 24 V power supply
(IN), 5-pin, male
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
WARNING
(Protective Extra Low Voltage) output voltages (maximum 60 V DC briefly) for all
connections and terminals of the electronics modules.
Delta connection
X02 - 24 V power supply
(OUT), 5-pin, female
4.11 Connecting the 24 V power supply
Pin
Signal
Description
1
2M
Switched 0 V
2
1M
Unswitched 0 V
3
FE
Not connected
4
1L+
Unswitched 24 V
5
2L+
Switched 24 V
Wiring
73

Advertisement

Table of Contents
loading

Table of Contents