Siemens SINAMICS G115D Operating Instructions Manual page 541

Distributed drive for conveyor technology control
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Procedure
To perform an acceptance test of the STO function as part of the basic functions, proceed as
follows:
1.
2.
3.
4.
You have performed the acceptance test of the STO function.
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
The converter is ready
The converter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
STO is not active (r9773.1 = 0).
Switch on motor
2.1.
Enter a speed setpoint ≠ 0.
2.2.
Switch on the motor (ON command).
2.3.
Check that the correct motor is running.
Select STO
3.1.
Select STO while the motor is running.
Test each configured activation, e.g. via digital inputs and PROFIsafe.
3.2.
Check the following:
When controlled via PROFIsafe
The converter signals the following:
"STO selection via PROFIsafe"
(r9772.20 = 1)
If a mechanical brake is not available, the motor coasts down.
A mechanical brake brakes the motor and holds it to ensure that it remains
at standstill.
The converter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
The converter signals the following:
"STO is selected" (r9773.0 = 1).
"STO is active" (r9773.1 = 1).
Deselect STO
4.1.
Deselect STO.
4.2.
Check the following:
STO is not active (r9773.1 = 0).
The converter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
A.2 Acceptance tests for the safety functions
When controlled via fail-safe digital
inputs (F-DI)
The converter signals the following:
"STO Selection via terminal"
(r9772.17 = 1)
Appendix
Status
539