List Of Alarms And Faults - Siemens SINAMICS G115D Operating Instructions Manual

Distributed drive
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Alarms, faults and system messages

8.6 List of alarms and faults

Parameter
p2126[0 ... 19]
p2127[0 ... 19]
For more information about this function, see function diagram 8075 and parameter
description in the List Manual.
8.6
List of alarms and faults
Overview
A message comprises a letter followed by the relevant number.
The letters have the following meaning:
A . . . .
F . . . .
The expressions have the following meaning:
CU/Power Module/power unit All refer to an Electronic Module.
Important alarms and faults
Number
Cause
F01000
Software fault in CU
F01001
Floating Point Exception
F01015
Software fault in CU
F01018
Power-up aborted more than once
A01028
Configuration error
F01033
Unit switchover: Reference param-
eter value invalid
308
Description
Changing the acknowledge-
ment mode, fault number
Changing the acknowledge-
ment mode
Alarm code . . . .
Fault code . . . .
For example, replacing a CU, Power Module, or power unit
means replacing an Electronic Module.
Remedy
Replace CU.
Switch CU off and on again.
Upgrade firmware or contact technical support.
1. Switch the module off and on again.
2. After this fault has been output, the module is booted with the factory
settings.
3. Recommission the converter.
Explanation: Parameterization on the memory card has been created with
a different type of module (article number, MLFB)
Check the module parameters and recommission if necessary.
Set the value of the reference parameter not equal to 0.0 (p0304, p0305,
p0310, p0596, p2000, p2001, p2002, p2003, r2004).
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
Setting
Selects the faults for which the acknowledge
mode is to be changed.
Factory setting: 0
Sets the acknowledgement type for the selected
fault:
1: Acknowledgement only using POWER ON
2: Immediate acknowledgement after removing
the fault cause
Factory setting: 1