Data backup and series commissioning

7.3 Other ways to back up settings

7.3
Other ways to back up settings
In addition to the default setting, the converter has an internal memory for backing up three
other settings.
On the memory card, you can back up 99 other settings in addition to the default setting.
(http://support.automation.siemens.com/WW/view/en/43512514)
7.4

Write protection

The write protection prevents unauthorized changing of the converter settings. If you are
working with Startdrive, write protection is only effective online. The offline project is not
write-protected.
Write protection is applicable for all user interfaces:
• Startdrive PC tool
• Parameter changes via fieldbus
• SINAMICS G120 Smart Access
No password is required for write protection.
Function description
Activate and deactivate write protection
Parameter
r7760
p7761
Exceptions to write protection
Parameters that can be changed with active write protection
Parameter
p0003
p0010
p0124[0...n]
p0970
p0971
p0972
314
Additional information is available on the Internet: Memory options
Description
Write protection/know-how pro-
tection status
Write protection
Description
Access level
Drive commissioning parameter filter
CU detection using LED
Reset drive parameters
Save parameters
Drive unit reset
Setting
Displays the status for the write protection and
know-how protection.
Bit 00: Write protection active
Setting for activating/deactivating the write pro-
tection for adjustable parameters.
0: Deactivate write protection
1: Activate write protection
Factory setting: 0
Setting
Sets the access level to read and write parameters.
Sets the parameter filter to commission a drive.
Identification of the Control Unit using an LED.
The parameter is used to initiate the reset of the
drive parameters.
Setting to save parameters in the non-volatile
memory.
Sets the required procedure to execute a hard-
ware reset for the drive unit.
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002