Automatic transfer
Precondition
The converter power supply has been switched off.
Procedure
1. Insert the memory card into the memory card slot.
2. Switch on the converter power supply.
If there is valid parameter data on the memory card, the converter accepts the data from the
memory card.
Transferring using Startdrive
Precondition
• A memory card is inserted in the converter.
• Connection between the PG/PC and converter has been properly established via a USB
cable or the fieldbus.
• You have installed the Startdrive commissioning tool on your PG/PC.
Procedure
1. Go online.
2. Proceed as follows to transfer parameter settings from the memory card to the converter.
3. Wait until Startdrive has signaled that the data transfer has been completed.
Note
After the transferring process has completed, safely remove the memory card.
You have transferred your settings from a memory card to the converter.
Your settings on the converter become effective after the next time you switch on its power
supply.
Transferring using SINAMICS G120 Smart Access
You can use the SINAMICS G120 Smart Access to transfer settings. For more information on
the transferring process, see Section "Backup and restore" in the SINAMICS G120 Smart
Access Operating Instructions.
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
Overview of the manuals (Page 542)
Data backup and series commissioning
7.1 Transferring settings using a memory card
309