Function description
You can use the DIP switches to perform basic commissioning and functional settings without
using additional commissioning tools.
When the DIP switches are in the OFF position (by default), the value of the function is
defined by the value of the according parameter(s) (see tables below). If the DIP switch is
activated for a specific function, then the parameter(s) for that function cannot be modified
by manually editing the parameter value.
Commissioning DIP switches 1.1 ... 1.6
DIP switch
DIP 1.1
DIP 1.2
DIP 1.3
DIP 1.4
DIP 1.5
DIP 1.6
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
Function
Motor temperature sensor type
Motor direction reversal
EM brake configuration
Pulse frequency
Motor type selection
87 Hz operation
Value
ON position
Pt1000
reversed
Brake according to sequence control
16 kHz
Reluctance motor
87 Hz operation possible in a delta
connection
Commissioning
5.4 Quick commissioning
OFF position
p0601
p1820
p1215
p1800
p0300
p0133
107