Example
Expand telegram 1 to 6 send words and 6 receive words.
Procedure
1. p0922 = 999
2. p2079 = 1
3. p2051[2] = r2050[2]
4. ...
5. p2051[5] = r2050[5]
6. Check the telegram length for the received and sent words:
– r2067[0] = 6
– r2067[1] = 6
You have expanded telegram 1 to 6 send words and 6 receive words.
❒
6.5.9
Acyclically reading and writing converter parameters
Overview
The converter supports the writing and reading of parameters via acyclic communication:
• For PROFINET: Write or read requests via B02E hex and B02F hex
Further information about acyclic communication is provided in the Fieldbus Function
Manual.
Application example, "Read and write to parameters"
Further information is provided on the Internet:
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
Overview of the manuals (Page 542)
Application examples (https://support.industry.siemens.com/cs/ww/en/view/29157692)
Advanced commissioning
6.5 Drive control via PROFINET
147