General Notes About Maintenance - Siemens SINAMICS G115D Operating Instructions Manual

Distributed drive for conveyor technology control
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Additional information on the SIMOGEAR geared motor
11.2 Specific data motor
Faults
Significant drop in
speed.
Protective equipment
trips.
11.2.15

General notes about maintenance

Unintentional starting of the drive unit
Secure the drive unit to prevent it from being started up unintentionally.
Attach a warning notice to the start switch.
NOTICE
Improper maintenance
Only authorized qualified personnel may perform the maintenance and servicing. Only
original parts supplied by Siemens AG may be installed.
Only qualified personnel may perform the inspection, maintenance and servicing work. Note
the information in the general notes and safety information (Page 404).
422
Causes
Insufficient ventilation.
Cooling air ducts dirty.
Coolant temperature outside
the permissible range.
Opposing torque too high.
Line voltage too low.
Phase interruption.
Incorrect circuit.
Overload.
Phase interruption.
Incorrect circuit.
Overload.
Switching frequency too high. Observe the rated duty.
Winding and terminal short-
circuit.
Starting time is exceeded.
WARNING
Remedy
Check the cooling air ducts, check the direc-
tion of rotation
Clean cooling air ducts.
Adjust the cooling air to the appropriate
temperature.
Check the motor torque and the load torque.
Check the line supply.
Check the connection to the line supply.
Observe the circuit diagram and rating plate.
Compare data on the rating plate.
Check the connection to the line supply.
Observe the circuit diagram and rating plate.
Compare data on the rating plate.
Measure the insulation resistance.
Check the run-up conditions.