Advanced commissioning
6.9 Conveyor technology control functions (for G115D PROFINET and AS-i variants only)
• With the end position shutdown activated (p3392 = 1), the following applies:
– If the motor runs in positive direction, it stops only when the stop sensor center
– If the motor runs in negative direction, it stops only when the stop sensor center
– A new ON command must be initiated to start the motor again. If the motor stops
– Setting the sensor bypass signal (p3390) to 1 overrides the stop sensor center signal
Note
The motor will have the following behavior with the end position shutdown (p3392 = 1) and
level-triggered sensor signals (p3394 = 1 or 2) activated:
• Once a stop sensor at the positive or negative position is triggered, the motor stops even if
the level is canceled.
• Once a stop sensor at the center position is triggered, the motor stops; if the level is
cancelled, then the motor runs again.
190
(p3386) or stop sensor positive direction (p3384) is triggered.
(p3386) or stop sensor negative direction (p3385) is triggered.
upon triggering the stop sensor positive direction/negative direction, the new
movement is only possible in the opposite direction.
p3386. In this case, the turntable can rotate directly from position 1 to position 3 and
vice versa.
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002