Siemens SINAMICS G115D Operating Instructions Manual page 304

Distributed drive for conveyor technology control
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Advanced commissioning
6.27 Calculating the energy saving for fluid flow machines
Flow characteristic
To set the characteristic, you require the following data from the machine manufacturer for
each speed interpolation point:
• The flow rate of the fluid-flow machine associated with the 5 selected converter speeds
• At constant speed, the power drawn which is associated with the 5 flow rates corresponds
to the line frequency and mechanical throttling of the flow rate.
Parameters
Parameter
r0039[0...2]
p0040
r0041
r0042[0...2]
p0043
p3320[0...n]
p3321[0...n]
p3322[0...n]
p3323[0...n]
302
Description
CO: Energy display [kWh]
Reset energy consumption display Setting p0040 = 1 to reset the display in r0039
Energy saved [kWh]
CO: Process energy display [Wh]
BI: Energy consumption display
enabled
Fluid flow machine power, point 1 [%]
Fluid flow machine speed, point 1 [%]
Fluid flow machine power, point 2 [%]
Fluid flow machine speed, point 2 [%]
Setting
[0] Energy consumption since the last reset.
[1] Energy drawn since the last reset.
[2] Energy fed back since the last reset.
r0039 serves as reference signal of r0042.
and r0041.
Factory setting: 0
Displays the saved energy referred to 100 operat-
ing hours. For an operating time of below 100
hours, the display is interpolated up to 100 hours.
[0] Energy consumption since the last reset.
[1] Energy drawn since the last reset.
[2] Energy fed back since the last reset.
For display as process variable. Enable with p0043.
Sets the signal source (BI: p0043 = 1 signal) to
enable/reset the process energy display in r0042.
Factory setting: 0
Specifies the power (P) of point 1 as a [%].
Factory setting: 25
Specifies the speed (n) of point 1 as a [%].
Factory setting: 0
Specifies the power (P) of point 2 as a [%].
Factory setting: 50
Specifies the speed (n) of point 2 as a [%].
Factory setting: 25
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002