Siemens SINAMICS G120 CU240B-2 Operating Instructions Manual

Siemens SINAMICS G120 CU240B-2 Operating Instructions Manual

With the control units
Hide thumbs Also See for SINAMICS G120 CU240B-2:
Table of Contents

Advertisement

SINAMICS G120
Frequency inverter
with the Control Units CU240B-2
Operating Instructions · 07/2010
SINAMICS
Answers for industry.
CU240E-2
CU240B-2 DP
CU240E-2 DP
CU240E-2 F
CU240E-2 DP-F

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SINAMICS G120 CU240B-2

  • Page 1 SINAMICS G120 Frequency inverter with the Control Units CU240B-2 CU240E-2 CU240B-2 DP CU240E-2 DP CU240E-2 F CU240E-2 DP-F Operating Instructions · 07/2010 SINAMICS Answers for industry.
  • Page 3 ___________________ Inverter with CU240B-2 and CU240E-2 Introduction Control Units ___________________ Description ___________________ Connecting SINAMICS ___________________ Commissioning SINAMICS G120 ___________________ Configuring the terminal Inverter with CU240B-2 and block CU240E-2 Control Units ___________________ Connection to a fieldbus Operating Instructions ___________________ Functions ___________________ Service and maintenance ___________________ Alarms, faults and system...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Table of contents Introduction.............................. 11 About this manual ........................11 Guide through this manual......................12 Overview of documentation ......................13 Adapting the inverter in line with the application................15 1.4.1 General basics ..........................15 1.4.2 Parameter ............................16 1.4.3 Parameters with follow-on parameterization................16 1.4.4 Parameter changes, which subsequently result in internal calculations........17 Frequently required parameters....................18 Extended scope for adaptation ....................20 1.6.1...
  • Page 6 Table of contents 4.3.3 Pre-assignment of the inputs and outputs .................. 62 4.3.4 Wiring examples for the factory settings ..................64 Commissioning with the BOP-2 ....................68 4.4.1 Inserting the BOP-2........................68 4.4.2 Display of the BOP-2........................68 4.4.3 Menu structure ..........................69 4.4.4 Changing parameter values.
  • Page 7 Table of contents 6.3.4 Acyclic communication.......................123 6.3.4.1 Acyclic communication over PROFIBUS DP (DP V1) ...............123 6.3.5 STEP 7 program examples......................124 6.3.5.1 STEP 7 program example for cyclic communication ..............124 6.3.5.2 STEP 7 program example for acyclic communication ...............126 Communication via RS485 ......................130 6.4.1 Integrating inverters into a bus system via the RS485 interface ..........130 6.4.2...
  • Page 8 Table of contents 7.7.6 Load torque monitoring (system protection) ................181 7.7.7 Speed and load failure via digital input ..................183 Status messages........................186 7.8.1 Overview, evaluating the inverter state..................186 7.8.2 System runtime ......................... 186 Technological functions......................187 7.9.1 Braking functions of the inverter ....................
  • Page 9 Table of contents List of faults ..........................256 Technical data ............................261 10.1 Technical data, CU240B-2 Control Unit..................261 10.2 Technical data, CU240E-2 Control Unit..................262 10.3 Technical data, Power Modules....................263 10.3.1 Technical data, PM240 ......................265 10.3.2 Technical data, PM240-2 ......................271 10.3.3 Technical data, PM250 ......................274 10.3.4 Technical data, PM250-2 ......................277 10.3.5...
  • Page 10 Table of contents Inverter with CU240B-2 and CU240E-2 Control Units Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA...
  • Page 11: Introduction

    If you encounter mistakes when reading this manual or if you have any suggestions for how it can be improved, please contact us at the following address or send your suggestion by E- mail: Siemens AG Drive Technologies Motion Control Systems...
  • Page 12: Guide Through This Manual

    Introduction 1.2 Guide through this manual Guide through this manual In this manual, you will find background information on your inverter, as well as a full description of the commissioning procedure: ① Should you be unfamiliar with assigning parameters to the inverter, background information can be found here: ...
  • Page 13: Overview Of Documentation

    Introduction 1.3 Overview of documentation Overview of documentation Manuals and software are available for every inverter application: Table 1- 1 Documentation for SINAMICS G120 Planning and configuring Installation and Commissioning Service and maintenance connection SIZER engineering tool Configuration Manual Selecting geared motors, motors and inverters using calculation examples...
  • Page 14 SIZER You obtain SIZER on a DVD (Order number: 6SL3070-0AA00-0AG0) and can be downloaded from the Internet: SIZER (http://support.automation.siemens.com/WW/view/en/10804987/130000) Configuration Manual You can obtain the Configuration Manual from your local sales office STARTER You obtain STARTER on a DVD (Order number: 6SL3072-0AA00-0AG0) and can be downloaded from the Internet: STARTER (http://support.automation.siemens.com/WW/view/en/10804985/130000)
  • Page 15: Adapting The Inverter In Line With The Application

    Introduction 1.4 Adapting the inverter in line with the application Adapting the inverter in line with the application 1.4.1 General basics Adapting the inverter to the drive task By means of commissioning with prompting, the inverter is adapted to the motor and the drive task so that the motor can be optimally operated and protected.
  • Page 16: Parameter

    Introduction 1.4 Adapting the inverter in line with the application 1.4.2 Parameter There are two types of parameters, adjustable and display parameters. Adjustable parameters Adjustable parameters are preceded with the letter "P". You can change the value of these parameters within a defined range. Example: P0305 is the parameter for the rated motor current in Amps.
  • Page 17: Parameter Changes, Which Subsequently Result In Internal Calculations

    Introduction 1.4 Adapting the inverter in line with the application ● New functions are assigned to the digital inputs (P0701 ... P0713) ● New functions are assigned to the digital outputs (P0731 ... P0733) ● Inverter control is interconnected with the signals from the digital inputs (P0800, P0801, P0840, etc.) You will find more information about follow-on parameterization for P0700 in the List Manual.
  • Page 18: Frequently Required Parameters

    Introduction 1.5 Frequently required parameters Frequently required parameters Parameters that in many cases help Table 1- 2 How to switch to commissioning mode or restore the factory setting Parameter Description P0010 Commissioning parameters 0: Ready (factory setting) 1: Perform quick commissioning 3: Perform motor commissioning 5: Technological applications and units 15: Define number of data records...
  • Page 19 Introduction 1.5 Frequently required parameters Table 1- 7 This is how you set the closed-loop type Parameter Description P1300 0: V/f control with linear characteristic 1: V/f control with linear characteristic and FCC 2: V/f control with parabolic characteristic 3: V/f control with parameterizable characteristic 4: V/f control with linear characteristic and ECO 5: V/f control for drives requiring a precise frequency (textile area) 6: V/f control for drive requiring a precise frequency and FCC...
  • Page 20: Extended Scope For Adaptation

    Introduction 1.6 Extended scope for adaptation Extended scope for adaptation 1.6.1 BICO technology: basic principles Principle of operation of BICO technology Open/closed-loop control functions, communication functions as well as diagnostic and operator functions are implemented in the inverter. Every function comprises one or several BICO blocks that are interconnected with one another.
  • Page 21 Introduction 1.6 Extended scope for adaptation Definition of BICO technology BICO technology represents a type of parameterization that can be used to disconnect all internal signal interconnections between BICO blocks or establish new connections. This is realized using Binectors and Connectors. Hence the name BICO technology. ( Binector Connector Technology) BICO parameters You can use the BICO parameters to define the sources of the input signals of a block.
  • Page 22: Bico Technology: Example

    Introduction 1.6 Extended scope for adaptation What sources of information do you need to help you set parameters using BICO technology? ● This manual is sufficient for simple signal interconnections, e.g. assigning a different significance to the to digital inputs. ●...
  • Page 23 Introduction 1.6 Extended scope for adaptation Parameter Description P20162 = 430 Run sequence of the time block within runtime group 5 (processing before the AND logic block) P20032 = 5 The AND logic block is enabled by assigning to runtime group 5 (time slice of 128 ms) P20033 = 440 Run sequence of the AND logic block within runtime group 5 (processing...
  • Page 24 Introduction 1.6 Extended scope for adaptation The "ON/OFF1 command" can now be interconnected again using BICO parameterization. The binector input of the BICO block ON/OFF1 is interconnected with the output of the AND logic block (P0840 = 20031). p0840[0] = 20031 p20030 p0840 Index [0]...
  • Page 25: Description

    Description Modularity of the converter system Thanks to their modular design, the inverters can be used in a wide range of applications with respect to functionality and power. The following overview describes the inverter components, which you require for your application.
  • Page 26: Overview Of Control Units

    Description 2.2 Overview of Control Units Memory card (MMC or SD) for carrying out standard commissioning of more than one inverter and for external data backup. PC Connection Kit, comprising STARTER DVD and USB cable for connecting an inverter to a computer Components, which you require depending on your particular application Filters and reactors ●...
  • Page 27: Power Module

    Description 2.3 Power Module Power Module Power Modules are available in various degrees of protection with a different topology in the power range from between 0.37 kW up to 250 kW. The Power Modules are sub-divided into various frame sizes (FS). Figure 2-1 Power Module with degree of protection IP20, PM240, PM250, PM260 Figure 2-2...
  • Page 28 Description 2.3 Power Module PM250-2, 3AC 400V - power units capable of energy recovery Power range (LO) 0.55 kW 4 kW … 3 kW … 7.5 kW With integr. line filter, Class A ○/● ○/● PM260, 3AC 690V - power units capable of energy recovery Power range (LO) 11 kW 30 kW...
  • Page 29: Reactors And Filters

    Description 2.4 Reactors and filters Reactors and filters Overview Depending on the Power Module, the following combinations with filters and reactors are permitted: Power Module Line-side components Load-side components Line reactor Line filters Braking Sine-wave filter Output reactor class B resistor PM240 ●...
  • Page 30 Description 2.4 Reactors and filters Inverter with CU240B-2 and CU240E-2 Control Units Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA...
  • Page 31: Connecting

    Installing Control Unit (Page 50) You will find details on how to install the inverter in the Internet: Hardware Installation Manual (http://support.automation.siemens.com/WW/view/en/30563173/133300). You can start to commission the inverter once installation has been completed. Inverter with CU240B-2 and CU240E-2 Control Units...
  • Page 32: Installing Reactors And Filters

    Connecting 3.2 Installing reactors and filters Installing reactors and filters Fitting inverter system components in space-saving manner Many inverter system components are designed as base components, that is, the component is mounted on the baseplate and the inverter mounted above it to save space. Up to two base components can be mounted above one another.
  • Page 33: Installing The Power Module

    Connecting 3.3 Installing the Power Module PM250 Line Line supply Line filter supply Power Line filter Output reactor or Power Modules sine-wave filter Module to the motor Basic layout of a PM250 Power Module with class Basic layout of a PM250 Power Module with a B line filter as a base component class B line filter as a base component and output reactor or sine-wave filter...
  • Page 34: Dimensions, Hole Drilling Templates, Minimum Clearances, Tightening Torques

    Connecting 3.3 Installing the Power Module Notes for installing Power Modules The Power Module must not be installed horizontally. Devices that could impede the flow of cooling air must not be installed in this area. Make sure that the ventilation openings for the cooling air for the inverter are not covered and that the flow of cooling air is not obstructed.
  • Page 35 Connecting 3.3 Installing the Power Module Dimensions and drilling patterns for the PM240 Power Modules Figure 3-1 PM240 dimension drawing Table 3- 1 Dimensions for the PM240 Power Modules, IP20 PM240 Power Dimensions Clearances IP20 Height Width Depth bottom lateral 0,37 …...
  • Page 36 Connecting 3.3 Installing the Power Module PM240 Power Dimensions Clearances IP20 Height Width Depth bottom lateral 37 … 45 without inch 19,65 10,83 8,03 15,9 9,25 11,81 11,81 filter Fixing: M6 screws, Torque: 6 Nm / 53 lbf.in FSE with 37 …...
  • Page 37 Connecting 3.3 Installing the Power Module Dimensions and drilling patterns for the PM240-2 Power Modules Figure 3-2 Dimensions and drilling pattern, PM240-2 IP20 Table 3- 2 Power Modules PM240-2, IP20 PM240-2 Power Dimensions Clearances IP20 Height Width Depth bottom lateral 0,55 …...
  • Page 38 Connecting 3.3 Installing the Power Module Figure 3-3 Dimensions and drilling pattern, PM240-2 PT Table 3- 3 Power Module PM240-2, push-through PM240-2 Power Dimensions Clearances Heigh Width Depth bottom lateral 2,2 … 3 without / inch 8,90 4,96 6,50 4,06 4,17 7,04 0,35...
  • Page 39 Connecting 3.3 Installing the Power Module Dimensions and drilling patterns for the PM250 Power Modules Figure 3-4 Dimensions and drilling patterns, PM250 Table 3- 4 PM250 Power modules, IP20 PM250 Power Dimensions Clearances IP20 Height Width Depth bottom lateral 7,5 … 15 inch 13,15 7,44...
  • Page 40 Connecting 3.3 Installing the Power Module PM250 Power Dimensions Clearances IP20 Height Width Depth bottom lateral FSF with 55 … 90 filter, inch 36,77 13,78 12,44 35,39 11,81 0,43 13,78 13,78 Class A Fixing: M8 screws, Torque: 13 Nm / 115 lbf.in *) up to 40 °C without any lateral clearance Dimensions and drilling patterns for the PM250-2 Power Modules Figure 3-5...
  • Page 41 Connecting 3.3 Installing the Power Module Figure 3-6 Dimensions and drilling pattern, M250-2, PT Table 3- 6 Power Module PM250-2, push-through PM250-2 Power Dimensions Clearances Heigh Width Depth bottom lateral without / inch 8,90 4,96 6,50 4,06 4,17 7,04 0,35 3,46 3,94 3,94...
  • Page 42 Connecting 3.3 Installing the Power Module Dimensions and drilling patterns of the Power Modules Figure 3-7 Dimensions and drilling pattern PM260 Table 3- 7 Power Module PM260, IP20 PM260 Power Dimensions Clearances IP20 Height Width Depth bottom lateral without / inch 20,12 10,83...
  • Page 43: Connection Overview For Power Module

    Connecting 3.3 Installing the Power Module 3.3.3 Connection overview for Power Module Figure 3-8 Connections for PM240 and PM250 Power Modules In addition to the Power Modules shown above, you can also combine Control Units with a PM260 Power Module. The PM260 connection corresponds to that of a PM250, however, a sine-wave filter is integrated in the PM260.
  • Page 44: Connecting The Line Supply And Motor

    Connecting 3.3 Installing the Power Module 3.3.4 Connecting the line supply and motor Preconditions Once the inverter has been properly installed, the line and motor connections can now be established. The following warning information must be observed here. WARNING Line and motor connections The inverter must be grounded on the line supply and motor side.
  • Page 45 Connecting 3.3 Installing the Power Module Connecting the motor: Star connection and delta connection With SIEMENS motors, you will see a diagram of both connection methods on the inside of the cover of the terminal box:  Star connection (Y) ...
  • Page 46: Emc-Compliant Connection

    Connecting 3.3 Installing the Power Module Line supply connection ● Connect the line supply to terminals U1/L1, V1/L2 and W1/L3. ● Connect the protective conductor of the line supply to terminal PE of the inverter. ● If available, close the terminal covers of the inverter. Note Inverters without an integrated line filter can be connected to grounded (TN, TT) and non- grounded (IT) line supply systems.
  • Page 47 Connecting 3.3 Installing the Power Module Cable routing and shielding ● All inverter power cables (line supply cables, connecting cables between the braking chopper and the associated braking resistance as well as the motor cables) must be separately routed away from signal and data cables. The minimum clearance should be approx.
  • Page 48 Connecting 3.3 Installing the Power Module EMC-compliant installation of Power Modules in degree of protection IP20 The EMC-compliant installation of power modules is shown in the following diagram using two examples. ① Line supply connection ② Motor connection ③ Metal mounting plate (unpainted and with a good electrical conductivity) ④...
  • Page 49 Connecting 3.3 Installing the Power Module Shielding with shield connection kit: Shield connection kits are available for all Power Module frame sizes (you will find more information in Catalog D11.1). The cable shields must be connected to the shield connection kit through the greatest possible surface area using shield clamps.
  • Page 50: Installing Control Unit

    Connecting 3.4 Installing Control Unit Installing Control Unit 3.4.1 Snapping the Control Unit onto the Power Module IP20 Power Modules Figure 3-10 Insert the Control Unit on the Power Module and then remove To gain access to the terminal strips, open the top and bottom front doors to the right. The terminal strips use spring-loaded terminals.
  • Page 51: Interfaces, Connectors, Switches, Terminal Blocks And Leds Of The Cu

    Connecting 3.4 Installing Control Unit 3.4.2 Interfaces, connectors, switches, terminal blocks and LEDs of the CU 31 +24V IN 31 31 32 GND IN 32 32 34 DI COM2 34 34 10 10 10 AI 1+ 11 11 11 AI 1- 26 26 26 AO 1+ 27 27...
  • Page 52: Terminal Strips On Cu240B-2 And Cu240E-2 Control Units

    Connecting 3.4 Installing Control Unit 3.4.3 Terminal strips on CU240B-2 and CU240E-2 Control Units Figure 3-12 Terminal strip on CU240B-2 and CU240B-2 DP If you require more than four digital inputs, use analog input AI 0 as additional digital input DI 11.
  • Page 53 Connecting 3.4 Installing Control Unit Figure 3-13 Terminal strip on CU240E-2, CU240E-2 F, CU240E-2 DP and CU240E-2 DP-F If you require more than six digital inputs, use analog inputs AI 0 or AI 1 as additional digital inputs DI 11 or DI 12. CAUTION If your application requires UL certification, please observe the note regarding the digital output in Section Technical data, CU240E-2 Control Unit (Page 262).
  • Page 54: Wiring Terminal Strips

    Connecting 3.4 Installing Control Unit If you wish to use several fail-safe digital inputs of the inverter, this is described in the Safety Integrated Function Manual. You will find the link to the Safety Integrated Function Manual in Section Overview of documentation (Page 13). Additional information on fail-safe digital inputs is available in Chapter Permitted sensors (Page 214).
  • Page 55: Commissioning

    Commissioning Typical commissioning scenarios After installation, you need to commission the inverter to set the inverter functions such that the inverter/motor combination is best adapted to the drive task. The inverter's functions and parameters are accessed either via the Operator Panel (BOP-2 or IOP) or the STARTER commissioning tool from a PC.
  • Page 56 Commissioning 4.1 Typical commissioning scenarios Commissioning guidelines ① Preparing commissioning (Page 57) ② Commissioning with factory settings (Page 60) ③ Commissioning with the BOP-2 (Page 68) Commissioning with STARTER (Page 73) ④ Connection to a fieldbus (Page 103) ⑤ Configuring the terminal block (Page 93) ⑥...
  • Page 57: Preparing Commissioning

    Commissioning 4.2 Preparing commissioning Users can access the inverter parameters via the following interfaces E:4 S C-V3N97875 SINAMICS MICRO MEMORY CARD 6 S L 3 2 5 4 - 0 A M 0 0 - 0 A A 0 Figure 4-2 Inverter's parameterization interfaces Preparing commissioning Prerequisites: before you start...
  • Page 58 Motor data / data on the motor rating plate If you use the STARTER commissioning tool and a SIEMENS motor, you only have to specify the motor Order No. In all other cases, you must read-off the data from the motor rating plate and enter into the appropriate parameters.
  • Page 59 Commissioning 4.2 Preparing commissioning What type of control is needed for the application? [P1300] A distinction is made between V/f open-loop control and vector closed-loop control. ● The V/f open-loop control is the simplest operating mode for an inverter. For example, it is used for applications involving pumps, fans or motors with belt drives.
  • Page 60: Commissioning With Factory Settings

    Commissioning 4.3 Commissioning with factory settings Commissioning with factory settings 4.3.1 Prerequisites for using the factory settings Prerequisites for using the factory settings In simple applications, commissioning can be carried out just using the factory settings. This section explains what prerequisites must be fulfilled for this purpose and how they are fulfilled.
  • Page 61 Commissioning 4.3 Commissioning with factory settings Table 4- 1 Command and setpoint sources Parameter Description P0700 = 2 or 6 Select the command source 2: Digital inputs (P0701 … P0709) (factory setting for CUs without PROFIBUS interface) 6: Fieldbus (P2050 … P2091), (factory setting for CUs with PROFIBUS DP interface) P1000 = 2 or 6 Select the setpoint source 2: Analog setpoint (factory setting for CUs without PROFIBUS DP interface)
  • Page 62: Pre-Assignment Of The Inputs And Outputs

    Commissioning 4.3 Commissioning with factory settings 4.3.3 Pre-assignment of the inputs and outputs Terminal strip factory settings Digital inputs Terminal Abbreviation Parameter Factory setting Meaning of the factory setting P0701 1 or 0 ON/OFF1 P0702 12 or 0 Direction reversal P0703 Fault acknowledgment P0704...
  • Page 63 Commissioning 4.3 Commissioning with factory settings Analog outputs Terminal Abbreviation Parameter Factory setting Meaning of the factory setting AO0+ P0771[0] Analog output is locked; can be switched from voltage output to current output by AO0- means of P0776 AO1+ P0771[1] Analog output is locked;...
  • Page 64: Wiring Examples For The Factory Settings

    Commissioning 4.3 Commissioning with factory settings 4.3.4 Wiring examples for the factory settings To ensure that the factory setting can be used, you must wire the terminal strip of your inverter as shown in the following examples. Pre-assignment of the terminal strip for the CU240B-2 Figure 4-3 CU240B-2: Wiring example for the factory settings Note...
  • Page 65 Commissioning 4.3 Commissioning with factory settings Pre-assignment of the terminal strip for the CU240B-2 DP Figure 4-4 CU240B-2 DP: Wiring example for the factory settings Note Assignment of the terminal strip after basic commissioning The CU240B-2 DP Control Unit is assigned in the same way as the CU240B-2 (without PROFIBUS interface) when you deselect bus communication for both the command sources and the setpoint value specification during basic commissioning of the inverter.
  • Page 66 Commissioning 4.3 Commissioning with factory settings Pre-assignment of the terminal strip for the CU240E-2 and CU240E-2 F Figure 4-5 CU240E-2 and CU240E-2 F: Wiring example for the factory settings Note Assignment of the terminal strip after basic commissioning The assignment of the terminal strip does not change once you have performed the basic commissioning procedure.
  • Page 67 Commissioning 4.3 Commissioning with factory settings Pre-assignment of the terminal strip for the CU240E-2 DP and CU240E-2 DP-F Figure 4-6 CU240E-2 DP and CU240E-2 DP-F: Wiring example for the factory settings Note Assignment of the terminal strip after basic commissioning The CU240E-2 DP (F) Control Unit is assigned in the same way as the CU240E-2 (F) (without PROFIBUS interface) when you deselect bus communication for both the command sources and the setpoint value specification during basic commissioning of the inverter.
  • Page 68: Commissioning With The Bop-2

    Commissioning 4.4 Commissioning with the BOP-2 Commissioning with the BOP-2 4.4.1 Inserting the BOP-2 The "Basic Operator Panel-2" (BOP-2) is an operation and display instrument of the inverter. It is directly inserted onto a Control Unit. 4.4.2 Display of the BOP-2 Figure 4-7 Meaning of the display in the BOP-2 Inverter with CU240B-2 and CU240E-2 Control Units...
  • Page 69: Menu Structure

    Commissioning 4.4 Commissioning with the BOP-2 4.4.3 Menu structure ① Changing parameter values. ② Basic commissioning Inverter with CU240B-2 and CU240E-2 Control Units Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA...
  • Page 70: Changing Parameter Values

    Commissioning 4.4 Commissioning with the BOP-2 4.4.4 Changing parameter values. Use BOP-2 to change your inverter settings, by selecting the appropriate parameter number and changing the parameter value. Parameter values can be changed in the menu "PARAMS" and in the menu "SETUP" Select the parameter number ●...
  • Page 71: Basic Commissioning

    Commissioning 4.4 Commissioning with the BOP-2 4.4.5 Basic commissioning Table 4- 3 Set the parameters of this menu one after the other: Menu Remark In the BOP-2, select the menu "SETUP". Select Reset (Parameter p0970) if you wish to reset all parameters to the factory setting before the basic commissioning: NO →...
  • Page 72: Additional Settings

    Commissioning 4.4 Commissioning with the BOP-2 Menu Remark Minimum motor speed. Motor ramp-up time. Motor ramp-down time. Confirm that the basic commissioning has been completed (Parameter p3900): NO → YES → OK Identifying motor data Alarm A07791 is output as long as the inverter has not identified the motor data. You must switch on the motor (e.g.
  • Page 73: Commissioning With Starter

    ● A PC with installed STARTER software V4.1.5 or higher. Information on the actual STARTER version and a possibility of downloading it from the Internet under STARTER (http://support.automation.siemens.com/WW/view/en/26233208). ● The motor must be connected to the inverter. Note The STARTER screens show general examples. You may therefore find that a screen contains more or fewer setting options than are shown in these instructions.
  • Page 74: Installing Usb Drivers

    Commissioning 4.5 Commissioning with STARTER 4.5.3 Installing USB drivers Description You must install and set the USB driver if you are connecting your converter for the first time to your PC via the USB interface. To start the installation: ● Connect the inverter to the PC using the USB cable supplied ●...
  • Page 75: System Settings In The Pc/Pg For The Usb Interface

    Commissioning 4.5 Commissioning with STARTER 4.5.4 System settings in the PC/PG for the USB interface Additional settings for the USB interface Before you can commission the inverter using the computer, you must assign the USB interface to a COM interface in the range COM1 … COM7 using the control panel. The procedure is explained in the following paragraphs.
  • Page 76 Commissioning 4.5 Commissioning with STARTER If the USB-COM emulation is assigned to an address higher than COM7, open the properties window by double-clicking on the interface. There you will find the "Advanced" button under the "Port settings" tab. A click on this button opens the extended properties in which you can assign the COM connection number an address <...
  • Page 77: Creating A Starter Project

    Commissioning 4.5 Commissioning with STARTER 4.5.5 Creating a STARTER project If you still do not know STARTER, then we recommend that you commission the system using the project wizards. Procedure ● Switch on the inverter supply voltage. ● Launch the STARTER commissioning tool. ●...
  • Page 78 Commissioning 4.5 Commissioning with STARTER PG/PC - Set interface ● Select "PC COM-Port (USS)" from the list and click on "Properties …" ● If "PC COM-Port (USS)" is not available, click on "Select …" to install the "PC COM-Port (USS)" interface as shown in the "Install/Remove Interfaces" dialog box. Inverter with CU240B-2 and CU240E-2 Control Units Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA...
  • Page 79 Commissioning 4.5 Commissioning with STARTER ● If you have installed the PC COM-Port (USS) interface, close the dialog box and now call up "Properties - PC COM-Port (USS)". ● In this dialog box, select the COM address that you defined when setting the USB interface.
  • Page 80: Establishing An Online Connection Between The Pc And Converter (Going "Online")

    Commissioning 4.5 Commissioning with STARTER ● By clicking on "Continue" you start the search for available devices. ● In this dialog box, you can change the designation of your converter (no spaces or special characters). ● Click on "Continue" and close the following dialog box by clicking on "Complete". This means that you have generated the STARTER project and the inverter is inserted in the STARTER project tree.
  • Page 81: Basic Commissioning

    Commissioning 4.5 Commissioning with STARTER ● Click on "Load hardware configuration to PG" to save the online setup to your PC and create an online link between the inverter and PC. ● To conclude your entry, choose "Close". ● The status display changes from the "Offline mode" with blue background into the "Online mode"...
  • Page 82 Commissioning 4.5 Commissioning with STARTER Carry-out basic commissioning The configuration wizard guides you step by step through the commissioning procedure. After the basic commissioning, you can change all of the settings and make detailed changes. ● In the start dialog box of the basic commissioning, select the control mode of the motor. If you are not certain which control mode you require for your application, then initially select V/f control.
  • Page 83 Commissioning 4.5 Commissioning with STARTER ● We recommend the following setting in the dialog box "Calculate motor data": ● Set the check mark for "RAM to ROM (save data in the drive)" in order to save your data in the inverter so that it is not lost when the power fails: Identifying motor data If the inverter has still not identified the motor data, alarm A07791 is output.
  • Page 84: Additional Settings

    Commissioning 4.5 Commissioning with STARTER ● In the control panel, click on the "Assume control priority" button. Then set the check mark for "Enables" signals and switch-on the motor. The inverter identifies the motor data after it has been switched-on. The measurement can take several minutes.
  • Page 85 Commissioning 4.5 Commissioning with STARTER Changing parameter values using the expert list ● If you wish to specifically change parameters, then - as shown below - call the expert list; there, scroll to the parameter and then change its value. You close the expert list by double clicking on an entry in the STARTER project tree.
  • Page 86: Back-Up The Settings And Transfer

    Commissioning 4.6 Back-up the settings and transfer Back-up the settings and transfer 4.6.1 External data backup and series commissioning After commissioning, your settings are saved in the inverter so that they are protected against power failure. In addition, you should also save the parameters on a storage medium outside the inverter: By backing up your data on an external storage medium, if the inverter develops a defect, your settings will not be lost.
  • Page 87: Backing Up And Transferring Settings Using Bop-2

    Commissioning 4.6 Back-up the settings and transfer 4.6.3 Backing up and transferring settings using BOP-2 Transferring parameters from the inverter to the operator panel (upload) ● Start data transfer in the menu "OPTIONS" - "TO BOP". ● Wait until the BOP-2 signals that data transfer has been completed. Note Data transfer can can take several minutes.
  • Page 88 Commissioning 4.6 Back-up the settings and transfer Backing up your settings We recommend that you insert the card before switching on the inverter for the first time. The inverter then automatically ensures that the actual parameter setting is saved both in the inverter as well as on the card.
  • Page 89: Transferring The Setting From The Memory Card

    Commissioning 4.6 Back-up the settings and transfer Manual upload If you do not wish to switch off the inverter power supply or you do not have an empty memory card available, you will need to transfer the parameter setting to the memory card as follows: ...
  • Page 90: Safely Remove The Memory Card

    Commissioning 4.6 Back-up the settings and transfer Manual download If you do not want to switch off the power supply, then you must transfer the parameter setting into the inverter in the following way:  Insert the memory card into the Control Unit. The Control Unit power supply is switched-on.
  • Page 91: Other Ways To Back Up Settings

    Commissioning 4.6 Back-up the settings and transfer 4.6.7 Other ways to back up settings You can backup three additional settings of the parameters in memory areas of the inverter reserved for this purpose. You will find additional information in the List Manual under the following parameters: Parameter Description...
  • Page 92: Restoring The Factory Setting

    Commissioning 4.7 Restoring the factory setting Restoring the factory setting The inverter is reset to the delivery condition by restoring the parameters to the factory setting, with the exception of the following parameters. Note The reset operation is not applied to parameters p0014, p0100, p0201, p0205 or the communication parameters.
  • Page 93: Configuring The Terminal Block

    Configuring the terminal block Before you configure the inputs and outputs of the inverter, you should have completed the basic commissioning, see Chapter Commissioning (Page 55) . The assignment of the inputs and outputs in the factory setting and after the basic commissioning are listed in Chapter Wiring examples for the factory settings (Page 64).
  • Page 94 Configuring the terminal block 5.1 Digital inputs Table 5- 2 Terminals, that can be used as either digital or analog input Terminal Terminal for ... Parameter ... Analog input 0 p0712 = 0 ... Digital input 11 p0712 > 0: The reference potential is terminal 4..
  • Page 95: Fail-Safe Digital Input

    Configuring the terminal block 5.2 Fail-safe digital input Fail-safe digital input This manual describes "Basic Safety", i.e. the STO safety function with control via a fail-safe input. Additional safety functions and additional fail-safe digital inputs of the inverter ("Extended Safety") are described in the Safety Integrated Function Manual. You will find the link to the Safety Integrated Function Manual in Section Overview of documentation (Page 13).
  • Page 96: Digital Outputs

    Configuring the terminal block 5.3 Digital outputs Digital outputs Up to three digital outputs are available that can be programmed to display different inverter states, e.g. faults, alarms and upper limit violations. Table 5- 5 Pre-assignment of the digital outputs Terminal Digital output Pre-assignment Pre-assignment can...
  • Page 97: Analog Inputs

    Configuring the terminal block 5.4 Analog inputs Analog inputs Depending on the design of the Control Unit, the inverter features one or two analog inputs. Table 5- 7 Pre-assignment of the analog inputs Terminal Analog input Parameter Factory setting AI 0+ AI 0 p0756[0] Bipolar voltage input -10 V …...
  • Page 98 Configuring the terminal block 5.4 Analog inputs You must also set the DIP switch for the analog input on the Control Unit. The DIP switch is located on the Control Unit behind the lower front doors.  Voltage input: Switch position U (factory setting) ...
  • Page 99 Configuring the terminal block 5.4 Analog inputs Example: Setting the analog inputs to 4 - 20 mA Terminal No. Parameter Description Significance AI 0+ p0756[0] = 3 Analog input type 0 Setting DIP switch to current 2: Unipolar current input (0 mA input ("I"): AI 0- …20 mA)
  • Page 100: Analog Outputs

    Configuring the terminal block 5.5 Analog outputs Analog outputs The Control Unit has one or two analog outputs (AO) depending on its design. You can use the analog outputs to display a wide variety of signals, e.g. the actual speed, the actual output voltage or the actual output current.
  • Page 101 Configuring the terminal block 5.5 Analog outputs Analog output as voltage or current output Use parameter p0776 to define whether the analog output will be used as a voltage output (10 V) or a current output (20 mA). The following options are available: AO 0 Current output (factory setting) 0 mA …...
  • Page 102 Configuring the terminal block 5.5 Analog outputs Table 5- 12 Additional analog output settings Parameter Description p07xx[0]: AO 0 p07xx[1]: AO 1 p0773[x] Analog outputs smoothing time constant Smoothing time constant of 1st order low-pass filter for the analog outputs p0775[x] Activate absolute-value generation 0: No absolute-value generation (factory setting)
  • Page 103: Connection To A Fieldbus

    Connection to a fieldbus Before you connect the inverter to the field bus, you should have completed the basic commissioning, see Chapter Commissioning (Page 55) Fieldbus interfaces of the Control Units The Control Units are available in different versions for communication with higher-level controls with the subsequently listed fieldbus interfaces: Fieldbus Profile...
  • Page 104: Setting The Bus Address Via Dip Switch

    Connection to a fieldbus 6.2 Setting the bus address via DIP switch Control and status words Control and status words always comprise two bytes. Depending on the control type, the two bytes are differently interpreted as higher or lower significance. An example for transferring control and status words with a SIMATIC control is provided in Chapter STEP 7 program example for cyclic communication (Page 124).
  • Page 105: Communication Via Profibus

    To prevent this, the Control Unit must be connected to a separate 24 V power supply via terminals 31 (+24 V I ) and 32 (0 V I Permissible cable lengths, routing and shielding the PROFIBUS cable Information can be found in the Internet (http://support.automation.siemens.com/WW/view/en/1971286). 6.3.1 Configuring communication via PROFIBUS 6.3.1.1 Task The inverter is to be controlled from a central SIMATIC controller via PROFIBUS.
  • Page 106: Required Components

    Drive ES Basic is the basic software of the engineering system, which combines the drive technology and Siemens controllers. The STEP 7 Manager user interface acts as a basis with which Drive ES Basic is used to integrate drives in the automation environment with respect to communication, configuration, and data storage.
  • Page 107: Setting The Profibus Address

    Connection to a fieldbus 6.3 Communication via PROFIBUS 6.3.1.3 Setting the PROFIBUS address Setting the PROFIBUS address of the inverter The inverter's PROFIBUS address is set using DIP switches on the Control Unit or using p0918. Using p0918, the address can only be set if all DIP switches for the bus address are either set to "OFF"...
  • Page 108: Inverter Gsd

    You have two options to obtain the GSD for your inverter: – You can find the SINAMICS inverter GSD on the Internet (http://support.automation.siemens.com/WW/view/en/22339653/133100). – The GSD is saved in the inverter. The GSD is written to the memory card if you insert the memory card in the Control Unit and set p0804 to 12.
  • Page 109: Inserting The Inverter Into The Step 7 Project

    Connection to a fieldbus 6.3 Communication via PROFIBUS 6.3.1.6 Inserting the inverter into the STEP 7 project ● Install the GSD of the inverter in STEP 7 via HW Config (Menu "Options - Install GSD files"). Once the GSD has been installed, the inverter appears as "SINAMICS G120 CU240x-2 DP V4.3"...
  • Page 110 1. PROFIsafe module (if one is used) 2. PKW channel (if one is used) 3. Standard, SIEMENS or free telegram (if one is used) 4. Slave-to-slave module If you do not use one or several of the modules 1, 2 or 3, configure the remaining modules starting with the 1st slot.
  • Page 111: Communication Parameters

    Standard telegram 20, PZD-2/6 350: SIEMENS telegram 350, PZD-4/4 SIEMENS telegram 352, PZD-6/6 353: SIEMENS telegram 353, PZD-2/2, BW-PKW-4/4 354: SIEMENS telegram 354, PZD-6/6, BW-PKW-4/4 999: Free telegram configuring with BICO Using parameter p0922, you automatically interconnect the corresponding signals of the inverter to the telegram.
  • Page 112: Cyclic Communication

    Connection to a fieldbus 6.3 Communication via PROFIBUS 6.3.3 Cyclic communication The PROFIdrive profile defines different telegram types. Telegrams contain the data for cyclic communication with a defined meaning and sequence. The inverter has the telegram types listed in the table below. Table 6- 6 Inverter telegram types Telegram type (p0922)
  • Page 113: Control And Status Words

    Connection to a fieldbus 6.3 Communication via PROFIBUS Table 6- 8 Telegram status in the inverter Process data Control ⇒ inverter Inverter ⇒ control item Status of the received Bits 0…15 in the Defining the word to be Status of the sent word word received word sent...
  • Page 114 Connection to a fieldbus 6.3 Communication via PROFIBUS Control word 1 (STW1) Control word 1 (bits 0 … 10 in accordance with PROFIdrive profile and VIK/NAMUR, bits 11 … 15 specific to inverter). Table 6- 9 Control word 1 and interconnection with parameters in the inverter Bit Valu Significance Remarks...
  • Page 115 Connection to a fieldbus 6.3 Communication via PROFIBUS Control word 3 (STW3) Control word 3 has the following default assignment. You can change the assignment with BICO technology. Table 6- 10 Control word 3 and interconnection with parameters in the inverter Bit Valu Significance Remarks...
  • Page 116 Connection to a fieldbus 6.3 Communication via PROFIBUS Status word 1 (ZSW1) Status word 1 (bits 0 to 10 in accordance with PROFIdrive profile and VIK/NAMUR, bits 11 to 15 for SINAMICS G120 only). Table 6- 11 Status word 1 and interconnection with parameters in the inverter Bit Valu Significance Remarks...
  • Page 117 Connection to a fieldbus 6.3 Communication via PROFIBUS Status word 3 (ZSW3) Status word 3 has the following standard assignment. You can change the assignment with BICO technology. Table 6- 12 Status word 3 and interconnection with parameters in the inverter Bit Valu Significance Description...
  • Page 118: Data Structure Of The Parameter Channel

    Connection to a fieldbus 6.3 Communication via PROFIBUS 6.3.3.2 Data structure of the parameter channel Parameter channel You can write and read parameter values via the parameter channel, e.g. in order to monitor process data. The parameter channel always comprises four words. Figure 6-3 Structure of the parameter channel Parameter identifier (PKE), 1st word...
  • Page 119 Connection to a fieldbus 6.3 Communication via PROFIBUS Request Description Response identifier identifier positive negative Change parameter value (field, word) Change parameter value (field, double word) Request number of field elements Change parameter value (field, double word) and save in EEPROM Change parameter value (field, word) and save in EEPROM Change parameter value (double word) and save in EEPROM ↓...
  • Page 120 Connection to a fieldbus 6.3 Communication via PROFIBUS Table 6- 15 Error numbers for the response "Request cannot be processed" Description Comments Impermissible parameter number (PNU) Parameter does not exist Parameter value cannot be changed The parameter can only be read Minimum/maximum not achieved or –...
  • Page 121 Connection to a fieldbus 6.3 Communication via PROFIBUS Parameter index (IND) Figure 6-5 Structure of the parameter index (IND) ● For indexed parameters, select the index of the parameter by transferring the appropriate value between 0 and 254 to the subindex within a job. ●...
  • Page 122 Connection to a fieldbus 6.3 Communication via PROFIBUS Example of read request for parameter P7841[2] To obtain the value of the indexed parameter P7841, you must fill the telegram of the parameter channel with the following data: ● Request parameter value (field): Bits 15 … 12 in the PKE word: Request identifier = 6 ●...
  • Page 123: Acyclic Communication

    The SIMATIC HMI can acyclically access parameters in the inverter. ● Instead of a SIEMENS startup tool or a SIMATIC HMI, it is also possible for an external master (Class 2 master) as defined in the acyclic parameter channel according to the PROFIdrive profile, Version 4.1 (with DS47), to access the inverter.
  • Page 124: Step 7 Program Examples

    Connection to a fieldbus 6.3 Communication via PROFIBUS 6.3.5 STEP 7 program examples 6.3.5.1 STEP 7 program example for cyclic communication S7 program for controlling the inverter In the following example, the control and inverter communicate via standard telegram 1. The control specifies control word 1 (STW1) and the speed setpoint, while the inverter responds with status word 1 (ZSW1) and its actual speed.
  • Page 125 Connection to a fieldbus 6.3 Communication via PROFIBUS Figure 6-7 Status evaluation of the inverter via PROFIBUS Information about the S7 program The hexadecimal numeric value 047E is written to control word 1. The bits of control word 1 are listed in the following table. Table 6- 18 Assignment of the control bits in the inverter to the SIMATIC flags and inputs Bit in...
  • Page 126: Step 7 Program Example For Acyclic Communication

    STEP 7 program example for acyclic communication Simple S7 program for parameterizing the inverter The number of simultaneous requests for acyclic communication is limited. More detailed information can be found in the Internet (http://support.automation.siemens.com/WW/view/en/15364459). M9.0 Starts reading parameters M9.2 displays the read process M9.1...
  • Page 127 Connection to a fieldbus 6.3 Communication via PROFIBUS FC1 to read parameters from the inverter Inverter parameters are read via SFC 58 and SFC 59. Inverter with CU240B-2 and CU240E-2 Control Units Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA...
  • Page 128 Connection to a fieldbus 6.3 Communication via PROFIBUS Figure 6-9 Function block for reading parameters You first have to define how many parameters (MB62), which parameter numbers (MW50, MW52, etc.), and how many parameter indices (MB58, MB59, etc.) are read for each parameter number.
  • Page 129 Connection to a fieldbus 6.3 Communication via PROFIBUS Once the read request has been issued and a waiting time of one second has elapsed, the parameter values are copied from the inverter via SFC 59 and saved in DB2. FC3 to write parameters to the inverter Figure 6-10 Function block for writing parameters You first have to define which value (MW35) is written to which parameter index (MW23) of...
  • Page 130: Communication Via Rs485

    Connection to a fieldbus 6.4 Communication via RS485 Communication via RS485 6.4.1 Integrating inverters into a bus system via the RS485 interface Connecting to a network via RS485 The Control Unit has a two-section terminal strip on its lower side which allows the inverter to be integrated into a bus system via the RS485 interface.
  • Page 131: Communication Via Uss

    Connection to a fieldbus 6.4 Communication via RS485 Figure 6-11 Communication network via RS485 6.4.2 Communication via USS 6.4.2.1 General information about communication with USS via RS485 Using the USS protocol (protocol of the universal serial interface), users can set up a serial data connection between a higher-level master system and several slave systems (RS 485 interface).
  • Page 132 Connection to a fieldbus 6.4 Communication via RS485 Additional communication settings Parameter Description p0700 = 6 Command source selection You set the command and setpoint source during the basic commissioning, see Selecting the fieldbus as command source Commissioning (Page 55) p1000 = 6 Speed setpoint selection Selecting the fieldbus as setpoint source...
  • Page 133: Structure Of A Uss Telegram

    Connection to a fieldbus 6.4 Communication via RS485 6.4.2.2 Structure of a USS telegram A USS telegram comprises a sequence of characters, which are sent in a defined sequence. The sequence of characters of a USS telegram is shown in the following diagram. Final information Header information...
  • Page 134 Connection to a fieldbus 6.4 Communication via RS485 LGE specifies the number of bytes that following in the telegram. It is defined as the sum of the following bytes ● Net data ● ADR ● BCC The actual overall telegram length is two bytes longer because STX and LGE are not counted in LGE.
  • Page 135: User Data Range Of The Uss Telegram

    Connection to a fieldbus 6.4 Communication via RS485 6.4.2.3 User data range of the USS telegram The user data range of the USS protocol is used to transmit application data. This comprises the parameter channel data and the process data (PZD). The user data occupy the bytes within the USS frame (STX, LGE, ADR, BCC).
  • Page 136 Connection to a fieldbus 6.4 Communication via RS485 Parameter identifier (PKE), 1st word The parameter identifier (PKE) is always a 16-bit value. Figure 6-14 PKE structure ● Bits 12 to 15 (AK) contain the request or response identifier. ● Bit 11 (SPM) is reserved and always = 0. ●...
  • Page 137 Connection to a fieldbus 6.4 Communication via RS485 Table 6- 21 Response identifier (inverter → master) Response identifier Description No response Transfer parameter value (word) Transfer parameter value (double word) Transfer descriptive element Transfer parameter value (field, word) Transfer parameter value (field, double word) Transfer number of field elements Request cannot be processed, task cannot be executed (with error number) 1) The required element of the parameter description is specified in IND (second word).
  • Page 138 Connection to a fieldbus 6.4 Communication via RS485 Description Comments Request not included / task is not After request identifier 5,11,12,13,14,15 supported No write access with enabled controller The operating state of the inverter prevents a parameter change 200/201 Changed minimum/maximum not The maximum or minimum can be limited achieved or exceeded further during operation.
  • Page 139 Connection to a fieldbus 6.4 Communication via RS485 Parameter value (PWE) You can vary the number of PWEs using parameter p2023. Parameter channel with fixed length Parameter channel with variable length P2023 = 4 P2023 = 127 A parameter channel with fixed length should For a variable length of parameter channel, the contain 4 words as this setting is sufficient for all master will only send the number of PWEs...
  • Page 140: Uss Read Request

    Connection to a fieldbus 6.4 Communication via RS485 6.4.2.5 USS read request Example: Reading out alarm messages from the inverter. The parameter channel comprises four words (p2023 = 4). In order to obtain the values of the indexed parameter r2122, you must fill the telegram of the parameter channel with the following data: ●...
  • Page 141: Uss Process Data Channel (Pzd)

    Connection to a fieldbus 6.4 Communication via RS485 ● Enter the offset of the parameter number in byte page index of word IND (2nd word): in this example = 0. ● Enter the index of parameter in the byte subindex of word IND (2nd word): for this example = 1 (CDS1) ●...
  • Page 142: Telegram Monitoring

    Connection to a fieldbus 6.4 Communication via RS485 The number of PZD words in a USS telegram is defined by parameter p2022. The first two words are: ● Control 1 (STW1, r0054) and main setpoint (HSW) ● Status word 1 (ZSW1, r0052) and main actual value (HIW) If P2022 is greater than or the same as 4, the additional control word (STW2, r0055) is transferred as the fourth PZD word (default setting).
  • Page 143 Connection to a fieldbus 6.4 Communication via RS485 The slave only responds after the response delay has expired. : : : : : : : : : : : : Figure 6-18 Start delay and response delay The duration of the start delay must at least be as long as the time for two characters and depends on the baud rate.
  • Page 144: Communication Over Modbus Rtu

    Connection to a fieldbus 6.4 Communication via RS485 6.4.3 Communication over Modbus RTU Overview of communication using Modbus The Modbus protocol is a communication protocol with linear topology based on a master/slave architecture. Modbus offers three transmission modes: ● Modbus ASCII Data is transferred in ASCII code.
  • Page 145 Connection to a fieldbus 6.4 Communication via RS485 The setting using DIP switches is described in Setting the bus address via DIP switch (Page 104). CAUTION A bus address that has been changed is only effective after switching-off and switching-on again.
  • Page 146: Modbus Rtu Telegram

    Connection to a fieldbus 6.4 Communication via RS485 Possible causes of a timeout Alarm Parameter Note name A1910 Setpoint timeout The alarm is generated when p2040 ≠ 0 ms and one of the following causes is present: The bus connection is interrupted ...
  • Page 147: Baud Rates And Mapping Tables

    Connection to a fieldbus 6.4 Communication via RS485 6.4.3.3 Baud rates and mapping tables Permissible baud rates and telegram delay The Modbus RTU telegram requires a pause for the following cases: ● Start detection ● Between the individual frames ● End detection Minimum duration: Processing time for 3.5 bytes (can be set via p2024[2]).
  • Page 148 Connection to a fieldbus 6.4 Communication via RS485 As a user, you can use both the register from the MM436 area and from the SINAMICS G120 area. The registers 40100 to 40111 are described as process data. A telegram monitoring time can be activated in p2040 for these registers.
  • Page 149 Connection to a fieldbus 6.4 Communication via RS485 Modbus Description Modb Unit Scaling On/Off text Data / parameter Reg. factor or value range acces Inverter identification 40300 Powerstack number 0 … 32767 r0200 40301 CU firmware 0.0001 0.00 … 327.67 r0018 Inverter data 40320...
  • Page 150: Write And Read Access Via Fc 3 And Fc 6

    Connection to a fieldbus 6.4 Communication via RS485 Modbus Description Modb Unit Scaling On/Off text Data / parameter Reg. factor or value range acces Technology controller adjustment 40510 Time constant for actual value filter of 0.00 … 60.0 p2265 the technology controller 40511 Scaling factor for actual value of the 0.00 …...
  • Page 151 Connection to a fieldbus 6.4 Communication via RS485 Table 6- 31 Structure of a read request for slave number 17 Example Byte Description 11 h Slave address 03 h Function code 00 h Register start address "High" (register 40110) 6D h Register start address "Low"...
  • Page 152: Communication Procedure

    Connection to a fieldbus 6.4 Communication via RS485 Table 6- 33 Structure of a write request for slave number 17 Example Byte Description 11 h Slave address 06 h Function code 00 h Register start address "High" (write register 40100) 63 h Register start address "Low"...
  • Page 153 Connection to a fieldbus 6.4 Communication via RS485 Logical error If the slave detects a logical error within a request, it responds to the master with an "exception response". In the response, the highest bit in the function code is set to 1. If the slave receives, for example, an unsupported function code from the master, the slave responds with an "exception response"...
  • Page 154 Connection to a fieldbus 6.4 Communication via RS485 Inverter with CU240B-2 and CU240E-2 Control Units Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA...
  • Page 155: Functions

    Functions Before you set the inverter functions, you should have completed the following commissioning steps: ● Commissioning (Page 55) ● If necessary: Configuring the terminal block (Page 93) ● If necessary: Connection to a fieldbus (Page 103) Overview of the inverter functions Figure 7-1 Overview of inverter functions Inverter with CU240B-2 and CU240E-2 Control Units...
  • Page 156 Functions 7.1 Overview of the inverter functions Functions relevant to all applications Functions required in special applications only The functions that you require in your application are The functions whose parameters you only need to adapt provided in the center of the function overview above. when actually required are located at the outer edge of the upper function overview.
  • Page 157: Inverter Control

    Functions 7.2 Inverter control Inverter control If the inverter is controlled using digital inputs, two control command define when the motor starts, stops and whether clockwise or counter-clockwise rotation is selected (two-wire control). Table 7- 1 Controlling the motor Control commands Explanation Two-wire control 1.
  • Page 158: Command Sources

    Functions 7.3 Command sources Table 7- 3 Parameterizing the function Parameter Description P0700 = 2 Controls the motor using the digital inputs of the inverter P0701 = 1 The motor is power-up with digital input 0 (factory setting) Further options: The motor can be powered-up with any other digital input, e.g.
  • Page 159: Setpoint Sources

    Functions 7.4 Setpoint sources Fieldbus as command source If you wish to control the motor via a fieldbus, you must connect the inverter to a higher-level control. For additional information, see chapter Connection to a fieldbus (Page 103). Setpoint sources 7.4.1 Selecting the setpoint source The setpoint source is the interface via which the inverter receives its setpoint.
  • Page 160: Analog Input As Setpoint Source

    Functions 7.4 Setpoint sources Adding setpoints from different sources Parameter P1000 can also be used to add more setpoint sources, e.g. you can specify the speed setpoint as the result of adding together the fieldbus and analog input setpoints. For more information, see the List Manual (P1000 in the parameter list and function diagram 3030).
  • Page 161 Functions 7.4 Setpoint sources Figure 7-3 Function chart of motorized potentiometer Motorized potentiometer parameters Table 7- 4 Basic setup of motorized potentiometer Parameter Description P1000 = 1 Select speed setpoint 1: Motorized potentiometer P1047 MOP ramp-up time (factory setting 10 s) P1048 MOP ramp-down time (factory setting 10 s) P1040...
  • Page 162 Functions 7.4 Setpoint sources Table 7- 5 Extended setup of motorized potentiometer Parameter Description P1030 Configuration of the MOP, parameter value with four independently adjustable bits 00 … 03 (factory setting 0110 bin) Bit 00: Save setpoint after switching off motor 0: After the motor is switched on, p1040 is specified as the setpoint 1: Setpoint is saved after the motor is switched off and set to the saved value once it is switched on...
  • Page 163: Fixed Speed As Setpoint Source

    Functions 7.4 Setpoint sources Example of parameterization of the motorized potentiometer Table 7- 6 Implementing a motorized potentiometer using digital inputs Parameter Description P0700 = 2 Command source Digital inputs P0701 = 1 Pre-assignment for digital input 0 The motor is switched on and off via digital input 0 P0702 = 13 Pre-assignment for digital input 1 The MOP setpoint is increased via digital input 1...
  • Page 164 Functions 7.4 Setpoint sources The various fixed setpoints can be selected in two ways: 1. Direct selection: Precisely one fixed speed setpoint is assigned to each selection signal (e.g. a digital input). As several selection signals are selected, the associated fixed speed setpoints are added together to from a total setpoint.
  • Page 165: Running The Motor In Jog Mode (Jog Function)

    Functions 7.4 Setpoint sources Example: Selecting two fixed speed setpoints using digital input 2 and digital input 3 The motor is to run at two different speeds: ● The motor is switched on with digital input 0 ● When digital input 2 is selected, the motor is to run at a speed of 300 rpm. ●...
  • Page 166: Specifying The Motor Speed Via The Fieldbus

    Functions 7.5 Setpoint calculation Table 7- 10 Parameters for the "Jog" function Parameters Description p1055 Signal source for jogging 1 - jog bit 0 (factory setting: 0) If you wish to jog via a digital input, then set p1055 = 722.x p1056 Signal source for jogging 2 - jog bit 1 (factory setting: 0) If you wish to jog via a digital input, then set p1056 = 722.x...
  • Page 167: Ramp-Function Generator

    Functions 7.5 Setpoint calculation The maximum speed also acts as an important reference value for various functions (e.g. the ramp-function generator). Table 7- 11 Parameters for minimum and maximum speed Parameter Description P1080 Minimum speed P1082 Maximum speed 7.5.2 Ramp-function generator The ramp-function generator in the setpoint channel limits the speed of changes to the speed setpoint.
  • Page 168: Motor Control

    Functions 7.6 Motor control The quick-stop function (OFF3) has a separate ramp-down time, which is set with P1135. Note If the ramp-up/down times are too short, the motor accelerates/decelerates with the maximum possible torque and the set times will be exceeded. Extended ramp-function generator In the extended ramp-function generator, the acceleration process can be made "softer"...
  • Page 169: V/F Control

    Functions 7.6 Motor control Examples of typical applications in which vector control is used: ● Hoisting gear and vertical conveyors ● Winders ● Extruders It is not permissible to use vector control in the following cases: ● If the motor is too small in comparison to the inverter (the rated motor power may not be less than one quarter of the rated inverter power) ●...
  • Page 170: V/F Control With Linear Characteristic

    Functions 7.6 Motor control 7.6.1.1 V/f control with linear characteristic V/f control with a linear characteristic is mainly used in applications in which the motor torque must be independent of the motor speed. Examples of such applications include horizontal conveyors or compressors.
  • Page 171: Additional Characteristics For The V/F Control

    Functions 7.6 Motor control 7.6.1.2 Additional characteristics for the V/f control In addition to linear and square-law characteristics, there are the following additional versions of the V/f control that are suitable for special applications. Table 7- 13 Additional V/f control versions (P1300) Parameter Application P1300 = 1...
  • Page 172: Optimizing With A High Break Loose Torque And Brief Overload

    Functions 7.6 Motor control 7.6.1.3 Optimizing with a high break loose torque and brief overload The ohmic losses in the motor stator resistance and the motor cable play a more significant role the smaller the motor and the lower the motor speed. You can compensate for these losses by raising the V/f characteristic.
  • Page 173: Vector Control

    Functions 7.6 Motor control Table 7- 14 Optimizing the starting characteristics for a linear characteristic Parameter Description P1310 Permanent voltage boost (factory setting 50 %) The voltage boost is effective from standstill up to the rated speed. It is at its highest at zero speed and reduces continuously as the speed increases. Value of voltage boost at zero speed in V: 1.732 ×...
  • Page 174: Torque Control

    Additional information about this function is provided in the parameter list and in function diagrams 6030 onwards in the List Manual. You will find more information On the Internet: (http://support.automation.siemens.com/WW/view/en/7494205): 7.6.2.3 Torque control Torque control is part of the vector control and normally receives its setpoint from the speed controller output.
  • Page 175: Protection Functions

    Functions 7.7 Protection functions Table 7- 16 The most important torque control parameters Parameter Description P1300 = … Control type: 20: Vector control without speed encoder 22: Torque control without speed encoder P0300 … Motor data are transferred from the motor rating plate during the quick commissioning P0360 and calculated with the motor data identification P1511 = …...
  • Page 176: Motor Temperature Monitoring Using A Temperature Sensor

    Functions 7.7 Protection functions Inverter response Parameter Description P0290 Power unit overload response(Factory setting for all Power Modules except for PM260: 2nd factory setting for PM260: 0) Setting the reaction to a thermal overload of the power unit: 0: Reduce output current (in vector control mode) or speed (in V/f mode) 1: No reduction, shutdown when overload threshold is reached (F30024) 2: Reduce pulse frequency and output current (in vector control mode) or pulse frequency and speed (in V/f mode)
  • Page 177 Functions 7.7 Protection functions Wire-break and short-circuit monitoring via KTY 84 ● Wire break: Resistance value > 2120 Ω ● Short circuit: Resistance value < 50 Ω As soon as a resistance outside this range is measured, A07015 "Alarm temperature sensor fault"...
  • Page 178: Protecting The Motor By Calculating The Motor Temperature

    Functions 7.7 Protection functions 7.7.3 Protecting the motor by calculating the motor temperature The temperature calculation is only possible in the vector control mode (P1300 ≥ 20) and functions by calculating a thermal motor model. Table 7- 18 Parameter to sense the temperature without using a temperature sensor Parameters Description P0621 = 1...
  • Page 179: Limiting The Maximum Dc Link Voltage

    Functions 7.7 Protection functions Settings NOTICE The factory setting of the I controller only needs to be changed in exceptional cases by appropriately trained personnel. Table 7- 19 controller parameters Parameter Description P0305 Rated motor current P0640 Motor current limit P1340 Proportional gain of the I controller for speed reduction...
  • Page 180 Functions 7.7 Protection functions Protecting the motor and inverter against overvoltage The V controller prevents – as far as is technically possible – the DC link voltage from DCmax reaching critical levels. The V controller is not suitable for applications in which the motor is permanently in the DCmax regenerative mode, e.g.
  • Page 181: Load Torque Monitoring (System Protection)

    Functions 7.7 Protection functions 7.7.6 Load torque monitoring (system protection) In many applications, it is advisable to monitor the motor torque: ● Applications where the load speed can be indirectly monitored by means of the load torque. For example, in fans and conveyor belts too low a torque indicates that the drive belt is torn.
  • Page 182 Functions 7.7 Protection functions Parameter Description Speed-dependent torque monitoring P2181 Load monitoring, response Setting the response when evaluating the load monitoring. 0: Load monitoring disabled >0: Load monitoring enabled P2182 Load monitoring, speed threshold 1 P2183 Load monitoring, speed threshold 2 P2184 Load monitoring, speed threshold 3 P2185...
  • Page 183: Speed And Load Failure Via Digital Input

    Functions 7.7 Protection functions 7.7.7 Speed and load failure via digital input With this function you can directly monitor not only the motor speed but also the speed of the driven load. Examples include: ● Gearbox monitoring, e.g. in traction drives or hoisting gear ●...
  • Page 184 Functions 7.7 Protection functions Table 7- 22 Setting load failure monitoring Parameter Description P2193 = 1…3 Load monitoring configuration (factory setting: 1) 0: Monitoring is disabled 1: Torque and load failure monitoring 2: Speed and load failure monitoring 3: Load failure monitoring P070x = 50 Pre-assignment of digital input 50: Load monitoring failure detection...
  • Page 185 Functions 7.7 Protection functions Table 7- 23 Setting speed deviation monitoring Parameter Description P2193 = 2 Load monitoring configuration (factory setting: 1) 2: Speed and load failure monitoring P2192 Load monitoring delay time (factory setting 10 s) Setting the delay time for evaluation of load monitoring P2181 Load monitoring response (factory setting 0) Setting the response for evaluation of load monitoring...
  • Page 186: Status Messages

    Functions 7.8 Status messages Status messages 7.8.1 Overview, evaluating the inverter state Information about the inverter state (alarms, faults, actual values) can be output via inputs and outputs and also via the communication interface. Details on evaluating the inverter state via inputs and outputs are provided in Section Configuring the terminal block (Page 93).
  • Page 187: Technological Functions

    Functions 7.9 Technological functions Technological functions The inverter offers a series of technology functions, e.g.: ● Braking functions ● Automatic restart and flying restart ● Basic process control functions ● Logical and arithmetic functions using function blocks that can be freely interconnected Please refer to the following sections for detailed descriptions.
  • Page 188 Functions 7.9 Technological functions Inverter braking methods Depending on the particular application, there are different methods for dealing with regenerative energy. DC braking Advantage: The motor is braked without the inverter  having to convert the regenerative energy Disadvantages: significant increase in the motor ...
  • Page 189 Functions 7.9 Technological functions Braking with regenerative feedback into the line supply Advantages: Constant braking torque; the regenerative  power is not converted into heat, but is regenerated into the line supply; can be used in all applications; continuous regenerative operation is possible - e.g. when lowering a crane load Disadvantage: Does not function when power fails...
  • Page 190: Dc Braking

    Functions 7.9 Technological functions 7.9.1.2 DC braking DC braking is typically used for applications in which the motor is normally operated at a constant speed and is only braked down to standstill in longer time intervals, e.g.: ● Centrifuges ● Saws ●...
  • Page 191 Functions 7.9 Technological functions CAUTION DC braking converts some of the kinetic energy of the motor and load into heat in the motor (temperature rise). The motor will overheat if the braking operation lasts too long or the motor is braked too often. Parameterizing DC braking Table 7- 26 DC braking enabling:...
  • Page 192: Compound Braking

    Functions 7.9 Technological functions 7.9.1.3 Compound braking Compound braking is typically used for applications in which the motor is normally operated at a constant speed and is only braked down to standstill in longer time intervals, e.g.: ● Centrifuges ● Saws ●...
  • Page 193 Functions 7.9 Technological functions Parameterizing compound braking Table 7- 28 Parameters to enable and set compound braking Parameter Description P3856 Compound braking current (%) With the compound braking current, the magnitude of the DC current is defined, which is additionally generated when stopping the motor for operation with V/f control to increase the braking effect.
  • Page 194: Dynamic Braking

    Functions 7.9 Technological functions 7.9.1.4 Dynamic braking Dynamic braking is typically used in applications in which dynamic motor behavior is required at different speeds or continuous direction changes, e.g.: ● Horizontal conveyors ● Vertical and inclined conveyors ● Hoisting gear Principle of operation The inverter controls the braking chopper depending on its DC link voltage.
  • Page 195 Braking resistor connection You will find more information about the braking resistor in the installation instructions for Power Module PM240 (http://support.automation.siemens.com/WW/view/en/30563173/133300). WARNING If an unsuitable braking resistor is used, this could result in a fire and severely damage the inverter.
  • Page 196: Braking With Regenerative Feedback To The Line

    Functions 7.9 Technological functions 7.9.1.5 Braking with regenerative feedback to the line Regenerative braking is typically used in applications where braking energy is generated either frequently or for longer periods of time, e.g.: ● Centrifuges ● Unwinders ● Cranes and hoisting gear Pre-requisite for regenerative braking is the Power Module PM250 or PM260.
  • Page 197: Motor Holding Brake

    The Brake Relay can be mounted on a mounting plate, the cabinet wall or the inverter's shield connection kit. For more information, refer to Installation instructions for the Brake Relay (http://support.automation.siemens.com/WW/view/en/23623179). Connect the Brake Relay to the Power Module using the cable form provided.
  • Page 198 Functions 7.9 Technological functions Connect the motor holding brake to the terminals of the Brake Relay. Figure 7-12 Connecting the motor holding brake Further information can be found in the Hardware Installation Manual for your Power Module. Principle of operation after OFF1 and OFF3 command Figure 7-13 Function diagram of the motor holding brake control after an OFF1 or OFF3 command Inverter with CU240B-2 and CU240E-2 Control Units...
  • Page 199 Functions 7.9 Technological functions The motor brake is controlled as shown in the following diagram: 1. After the ON command (switch on motor), the motor is magnetized. At the end of the magnetizing time (P0346) the inverter issues the command to open the brake. 2.
  • Page 200 Functions 7.9 Technological functions Principle of operation after OFF2 or STO command For the following signals, the brake closing time is not taken into account: ● OFF2 command ● For fail-safe applications, in addition, after "Safe Torque Off" (STO) After these control commands, the signal to close the motor holding brake is immediately output independent of the motor speed.
  • Page 201 Functions 7.9 Technological functions Commissioning WARNING The following applications require special settings of the motor holding brake. In these cases, the motor holding brake control may only be commissioned by experienced personnel:  All applications that involve moving and transporting people ...
  • Page 202 Functions 7.9 Technological functions Table 7- 31 Control logic parameters of the motor holding brake Parameter Description P1215 = 1 Enable motor holding brake 0 Motor holding brake locked (factory setting) 1 Motor holding brake just like the sequence control 2: Motor holding brake permanently open 3: Motor holding brake just like the sequential control, connected via BICO P1216...
  • Page 203: Automatic Restart And Flying Restart

    Functions 7.9 Technological functions 7.9.2 Automatic restart and flying restart 7.9.2.1 Flying restart – switching on while the motor is running If you switch on the motor while it is still running, then with a high degree of probability, a fault will occur due to overcurrent (overcurrent fault F07801).
  • Page 204 Functions 7.9 Technological functions Table 7- 34 Advanced settings Parameter Description P1201 Flying restart enable signal source (factory setting: 1) Defines a control command, e.g. a digital input, through which the flying restart function is enabled. P1202 Flying restart search current (factory setting 100 %) Defines the search current with respect to the motor magnetizing current (r0331), which flows in the motor while the flying restart function is being used.
  • Page 205: Automatic Switch-On

    Functions 7.9 Technological functions 7.9.2.2 Automatic switch-on The automatic restart includes two different functions: 1. The inverter automatically acknowledges faults. 2. After a fault occurs or after a power failure, the inverter automatically switches-on the motor again. This automatic restart function is primarily used in applications where the motor is controlled locally via the inverter's inputs.
  • Page 206 Functions 7.9 Technological functions ● Set the parameters of the automatic restart function. The method of operation of the parameters is explained in the following diagram and in the table. The inverter automatically acknowledges faults under the following conditions: p1210 = 1: always. ...
  • Page 207 Functions 7.9 Technological functions Table 7- 35 Overview of parameters to set the automatic restart Parameter Explanation p1210 Automatic restart mode (factory setting: 0) Disable automatic restart Acknowledge all faults without restarting Restart after power failure without further restart attempts Restart after fault with further restart attempts Restart after power failure after manual fault acknowledgement Restart after fault after manual fault acknowledgement...
  • Page 208 Functions 7.9 Technological functions Parameter Explanation p1213[0] Automatic restart monitoring time for restart (factory setting: 60 s) This parameter is only effective for the settings p1210 = 4, 6, 14, 16. With this monitoring function, you limit the time in which the inverter may attempt to automatically switch-on the motor again.
  • Page 209: Pid Technology Controller

    Functions 7.9 Technological functions 7.9.3 PID technology controller The technology controller permits all types of simple process controls to be implemented. You can use the technology controller for e.g. pressure controllers, level controls or flow controls. Figure 7-18 Example: technology controller as a level controller Principle of operation The technology controller specifies the speed setpoint of the motor in such a way that the process variable to be controlled corresponds to its setpoint.
  • Page 210: Logical And Arithmetic Functions Using Function Blocks

    Functions 7.9 Technological functions 7.9.4 Logical and arithmetic functions using function blocks Additional signal interconnections in the inverter can be established by means of free function blocks. Every digital and analog signal available via BICO technology can be routed to the appropriate inputs of the free function blocks. The outputs of the free function blocks are also interconnected to other functions using BICO technology.
  • Page 211 Functions 7.9 Technological functions Table 7- 37 Runtime groups and possible assignments of the free function blocks Runtime groups 1 … 6 with associated time slices Free function blocks 8 ms 16 ms 32 ms 64 ms 128 ms 256 ms Logic modules ✓...
  • Page 212 Functions 7.9 Technological functions Scaling examples ● Speed: Reference speed p2000 = 3000 rpm, actual speed 2100 rpm. As a consequence, the following applies to the scaled input quantity: 2100 / 3000 = 0.7. ● Temperature: Reference quantity is 100 °C. For an actual temperature of 120 °C, the input value is obtained from 120 °C / 100 °C = 1.2.
  • Page 213 BICO technology: example (Page 22)chapter. You can find additional information in the following manuals: ● Function Manual "Description of the Standard DCC Blocks" (http://support.automation.siemens.com/WW/view/en/29193002) ● Function Manual "Free Function Blocks" (http://support.automation.siemens.com/WW/view/en/35125827) Inverter with CU240B-2 and CU240E-2 Control Units...
  • Page 214: Safe Torque Off (Sto) Safety Function

    Functions 7.10 Safe Torque Off (STO) safety function 7.10 Safe Torque Off (STO) safety function These operating instructions describe the commissioning of the STO safety function when it is controlled via a fail-safe digital input. You will find a detailed description of all safety functions and control using PROFIsafe in the Safety Integrated Function Manual, see Section Overview of documentation (Page 13).
  • Page 215: Connecting Fail-Safe Digital Inputs

    Functions 7.10 Safe Torque Off (STO) safety function 7.10.3 Connecting fail-safe digital inputs On the following pages, you will find examples of connecting the fail-safe digital input from "Basic safety", in accordance with PL d according to EN 13849-1 and SIL2 according to IEC 61508 for the case that all of the components are installed in a control cabinet.
  • Page 216: F-Di Signal Filtering

    Functions 7.10 Safe Torque Off (STO) safety function Figure 7-23 Connecting an F digital output module, e.g. SIMATIC F digital output module You can find additional connection options and connections in separate control cabinets in the Safety Integrated Function Manual, see Section Overview of documentation (Page 13). 7.10.4 F-DI signal filtering The inverter checks the signals of the fail-safe digital input for consistency.
  • Page 217 Functions 7.10 Safe Torque Off (STO) safety function Figure 7-24 Filter for suppressing discrepancy monitoring The filter does not increase the inverter response time. The inverter activates its safety functions as soon as one of the two F-DI signals changes its state from high to low. Bit pattern test of fail-safe outputs and contact bounces of sensors The inverter normally responds immediately to signal changes at its fail-safe input.
  • Page 218 Functions 7.10 Safe Torque Off (STO) safety function If the signal to control STO is not "stable", then the inverter responds with a fault. (Definition of a stable signal: Following a change to the F-DI input signals, the inverter triggers an internal monitoring time. Up until the end of the time interval 5 x p9650, both input signals must have a constant signal level.
  • Page 219: Forced Dormant Error Detection

    Functions 7.10 Safe Torque Off (STO) safety function 7.10.5 Forced dormant error detection To fulfill the requirements of standards EN 954-1, ISO 13849-1 and IEC 61508 regarding timely error detection, the inverter must regularly test its safety-relevant circuits to ensure that they function correctly - this must be performed at least once every year.
  • Page 220: Password

    Functions 7.10 Safe Torque Off (STO) safety function 7.10.6 Password The safety functions are protected against unauthorized changes by a password. Note If you want to change the parameters of the safety functions, but do not know the password, please contact customer support. The factory setting for the password is "0".
  • Page 221: Defining Commissioning Method

    Functions 7.10 Safe Torque Off (STO) safety function 7.10.7.1 Defining commissioning method ● Select "STO via terminal". ● If you require the status signal "STO active" in your higher-level controller, interconnect it accordingly. ● Click the button to call up the advanced settings for STO. 7.10.7.2 Assigning parameters to the STO ●...
  • Page 222: Activate Settings

    Functions 7.10 Safe Torque Off (STO) safety function ● Set the following in the above screen: – ① ② F-DI input filter (debounce time) and monitoring for simultaneous operation (discrepancy): The method of functioning of the two filters is described in the section entitled F-DI signal filtering (Page 216).
  • Page 223 Functions 7.10 Safe Torque Off (STO) safety function ● Remove multiple assignments of the digital inputs: Figure 7-28 Example: automatic assignment of digital inputs DI 4 and DI 5 with STO Figure 7-29 Remove pre-assignment of digital inputs DI 4 and DI 5 ●...
  • Page 224: Acceptance Test - Following Completion Of Commissioning

    Functions 7.10 Safe Torque Off (STO) safety function 7.10.8 Acceptance test - following completion of commissioning 7.10.8.1 Prerequisites and authorized persons Requirements for acceptance tests are derived from the EC Machinery Directive and ISO 13849-1. ● Check the safety-related functions and machine parts following commissioning. ●...
  • Page 225: Reduced Acceptance Test

    Functions 7.10 Safe Torque Off (STO) safety function 7.10.8.3 Reduced acceptance test A complete acceptance test is only necessary following first commissioning. An acceptance test with a reduced scope is sufficient for expansions of safety functions. The reduced acceptance tests must be carried out separately for each individual drive, as far as the machine allows.
  • Page 226: Documentation

    Functions 7.10 Safe Torque Off (STO) safety function 7.10.8.4 Documentation Machine overview Enter your machine's data into the following table. Designation … Type … Serial number … Manufacturer … End customer … Overview image of the machine: … … … …...
  • Page 227 Functions 7.10 Safe Torque Off (STO) safety function Function table Fill in the following table for your machine. Mode of operation Safety device Drive Controlling the safety Status of the safety function function … … … … … … … …...
  • Page 228: Completion Of The Certificate

    Functions 7.10 Safe Torque Off (STO) safety function Description Status Switch on the motor (ON command). Ensure that the correct motor is running. Select STO while the motor is running Note: Test each configured activation, e.g. via digital inputs and PROFIsafe. Check the following: If a mechanical brake is not available, the motor coasts down.
  • Page 229 Functions 7.10 Safe Torque Off (STO) safety function In addition to the individual checksums of the parameters, the inverter calculates and saves the following values: 1. The "total" checksum across all checksums. 2. Time of the last parameter changed. Labeling the drive Checksums Processor 1 Processor 2...
  • Page 230: Switchover Between Different Settings

    Functions 7.11 Switchover between different settings 7.11 Switchover between different settings 7.11.1 Changing over the command data sets (manual, automatic) Switching over master control In some applications, the inverter is operated from different locations. Example: Switchover from the automatic mode into the manual mode A central control can switch a motor on/off or change its speed either via a fieldbus or via local switches.
  • Page 231 Functions 7.11 Switchover between different settings Figure 7-30 CDS switchover in the inverter Use parameter P0170 to define the number of command data sets (2, 3 or 4). Table 7- 42 Selecting the number of command data sets Parameter Description P0010 = 15 Drive commissioning: Data sets P0170...
  • Page 232 Functions 7.11 Switchover between different settings Table 7- 43 Command data set changeover using parameters P0810 and P0811. Status of binector P0810 Status of binector P0811 The command data set that is presently active has a gray background. CDS3 is only CDS2 is only available when available when...
  • Page 233: Switching Over Drive Data Sets (Different Motors Connected To An Inverter)

    Functions 7.11 Switchover between different settings A copy function is available making it easier to commission more than one command data set. Table 7- 45 Parameters for copying the command data sets Parameter Description P0809[0] Number of the command data set to be copied (source) P0809[1] Number of the command data set to which the data is to be copied (target) P0809[2] = 1...
  • Page 234 Functions 7.11 Switchover between different settings Figure 7-31 DDS switchover in the inverter Use parameter P0180 to define the number of command data sets (2, 3 or 4). Table 7- 46 Selecting the number of command data sets Parameter Description P0010 = 15 Drive commissioning: Data sets P0180...
  • Page 235 Functions 7.11 Switchover between different settings Table 7- 47 Parameters for switching the drive data sets: Parameter Description P0820 1st cntrol command for switching the drive data sets Example: When P0820 = 722.0, the system switches from drive data set 0 to drive data set 1 via digital input 0 P0821 2nd control command for switching the drive data sets...
  • Page 236 Functions 7.11 Switchover between different settings Inverter with CU240B-2 and CU240E-2 Control Units Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA...
  • Page 237: Service And Maintenance

    Service and maintenance Replacing the inverter components In the event of a long-term function fault, you can replace the inverter's Power Module or Control Unit separately. In many cases, you can switch the motor back on again straight after the replacement. Replacing components without recommissioning the drive In the scenarios listed below, the inverter can be used straight after components have been replaced:...
  • Page 238 Service and maintenance 8.1 Replacing the inverter components Component replacement Remark Replacing Control Unit with memory card with a Control Unit E:4 S C-V3N97875 SINAMICS MICRO MEMORY CARD 6 S L 3 2 5 4 - 0 A M 0 0 - 0 A A 0 of the same type and ...
  • Page 239: Replacing The Control Unit

    Service and maintenance 8.2 Replacing the Control Unit Component replacement without Replacing Control Unit a memory card E:4 S C-V3N97875 SINAMICS MICRO MEMORY CARD 6 S L 3 2 5 4 - 0 A M 0 0 - 0 A A 0 Replacing Control Unit with a Control Unit of a different type...
  • Page 240 Service and maintenance 8.2 Replacing the Control Unit Procedure for replacing a Control Unit without a memory card ● Disconnect the line voltage of the Power Module and (if installed) the external 24 V supply or the voltage for the relay outputs DO 0 and DO 2 of the Control Unit. ●...
  • Page 241: Replacing The Power Module

    Service and maintenance 8.3 Replacing the Power Module Replacing the Power Module Procedure for replacing a Power Module ● Disconnect the Power Module from the line. ● If present, switch off the 24 V supply of the Control Unit. ● After switching off the line voltage, wait 5 minutes until the device has discharged itself. ●...
  • Page 242 Service and maintenance 8.3 Replacing the Power Module Inverter with CU240B-2 and CU240E-2 Control Units Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA...
  • Page 243: Alarms, Faults And System Messages

    Alarms, faults and system messages The inverter has the following diagnostic types: ● LED You can obtain an overview of the inverter state locally at the Control Unit LED. ● Alarms and faults Alarms and faults have a unique number. The inverter displays the numbers on the Operator Panel and via STARTER - or signals them to a higher-level control.
  • Page 244: Operating States Indicated On Leds

    Alarms, faults and system messages 9.1 Operating states indicated on LEDs Operating states indicated on LEDs The LED RDY (Ready) is temporarily orange after the power supply voltage is switched-on. As soon as the color of the LED RDY changes to either red or green, the LEDs on the Control Unit indicate the inverter state.
  • Page 245 Alarms, faults and system messages 9.1 Operating states indicated on LEDs SAFE LED displays Table 9- 4 Diagnostics of the safety functions SAFE LED Meaning YELLOW - on One or more safety functions are enabled, but not active. YELLOW - slow One or more safety functions are active;...
  • Page 246: Alarms

    Alarms, faults and system messages 9.2 Alarms Alarms Alarms have the following properties: ● They do not have a direct effect in the inverter and disappear once the cause has been removed ● They do not need have to be acknowledged ●...
  • Page 247 Alarms, faults and system messages 9.2 Alarms Figure 9-3 Complete alarm buffer Emptying the alarm buffer: Alarm history The alarm history traces up to 56 alarms. The alarm history only takes alarms that have been removed from the alarm buffer. If the alarm buffer is completely filled - and an additional alarm occurs - then the inverter shifts all alarms that have been removed from the alarm buffer into the alarm history.
  • Page 248 Alarms, faults and system messages 9.2 Alarms Parameters of the alarm buffer and the alarm history Table 9- 5 Important parameters for alarms Parameter Description r2122 Alarm code Displays the numbers of alarms that have occurred r2123 Alarm time received in milliseconds Displays the time in milliseconds when the alarm occurred r2124 Alarm value...
  • Page 249: List Of Warnings

    Alarms, faults and system messages 9.3 List of warnings List of warnings Table 9- 7 The most important warnings Number Cause Remedy A01028 Configuration error Explanation: Parameterization on the memory card has been created with a different type of module (order number, MLFB) Check the module parameters and recommission if necessary.
  • Page 250 Alarms, faults and system messages 9.3 List of warnings Number Cause Remedy A07991 Motor data identification Switch on the motor and identify the motor data. activated A30920 Temperature sensor fault Check that the sensor is connected correctly. You will find additional information in the List Manual or in the STARTER online help. Table 9- 8 The most important alarms for safety functions Number...
  • Page 251: Faults

    Alarms, faults and system messages 9.4 Faults Faults A fault displays a severe fault during operation of the inverter. The inverter signals a fault as follows: ● at the Operator Panel with Fxxxxx ● at the Control Unit using the red LED RDY ●...
  • Page 252 Alarms, faults and system messages 9.4 Faults The fault buffer can accept up to eight actual faults. The next to last fault is overwritten if an additional fault occurs after the eighth fault. Figure 9-7 Complete fault buffer Fault acknowledgement In most cases, you have the following options to acknowledge a fault: ●...
  • Page 253 Alarms, faults and system messages 9.4 Faults Emptying the fault buffer: Fault history The fault history can contain up to 56 faults. The fault acknowledgement has no effect as long as none of the fault causes of the fault buffer have been removed. If at least one of the faults in the fault buffer has been removed (the cause of the fault has been removed) and you acknowledge the faults, then the following happens: 1.
  • Page 254 Alarms, faults and system messages 9.4 Faults Parameters of the fault buffer and the fault history Table 9- 9 Important parameters for faults Parameter Description r0945 Fault code Displays the numbers of faults that have occurred r0948 Fault time received in milliseconds Displays the time in milliseconds when the fault occurred r0949 Fault value...
  • Page 255 Alarms, faults and system messages 9.4 Faults Extended settings for faults Table 9- 10 Advanced settings Parameter Description You can change the fault response of the motor for up to 20 different fault codes: p2100 Setting the fault number for fault response Selecting the faults for which the fault response should be changed p2101 Setting, fault response...
  • Page 256: List Of Faults

    Alarms, faults and system messages 9.5 List of faults List of faults Table 9- 11 The most important faults Number Cause Remedy F01910 Fieldbus SS setpoint timeout Check the bus connection and communication partner, e.g. switch the PROFIBUS master to the RUN status. F03505 Analog input, wire break Check the connection to the signal source for interrupts.
  • Page 257 Alarms, faults and system messages 9.5 List of faults Number Cause Remedy F07900 Motor blocked Check that the motor can run freely. Check the torque limits (r1538 and r1539). Check the parameters of the "Motor blocked" message (P2175, P2177). F07901 Motor overspeed Activate precontrol of speed limiting controller (P1401 bit 7 = 1).
  • Page 258 Alarms, faults and system messages 9.5 List of faults Number Cause Remedy F30015 Motor cable phase failure Check the motor cables. Increase the ramp-up or ramp-down time (P1120). F30027 Time monitoring for DC link pre- Check the supply voltage on the input terminals. charging Check the line voltage setting (P0210).
  • Page 259 Alarms, faults and system messages 9.5 List of faults Table 9- 13 The most important faults for safety functions Number Cause Remedy F01600 STOP A initiated Select STO and then deselect again F01650 Acceptance test required Carry out acceptance test and create test certificate. Switch the Control Unit off and then on again.
  • Page 260 Alarms, faults and system messages 9.5 List of faults Inverter with CU240B-2 and CU240E-2 Control Units Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA...
  • Page 261: Technical Data

    Technical data 10.1 Technical data, CU240B-2 Control Unit Feature Data Operating voltage Supply from the Power Module or an external 24 V DC supply (20.4 V ... 28.8 V, 1 A) via control terminals 31 and 32 Heat loss 5.0 W plus power loss of output voltages Output voltages 18 V …...
  • Page 262: Technical Data, Cu240E-2 Control Unit

    Technical data 10.2 Technical data, CU240E-2 Control Unit 10.2 Technical data, CU240E-2 Control Unit Feature Data Operating voltage Supply from the Power Module or an external 24 V DC supply (20.4 V … 28.8 V, 0.5 A) via control terminals 31 and 32 Heat loss 5.0 W plus power loss of output voltages Output voltages...
  • Page 263: Technical Data, Power Modules

    Technical data 10.3 Technical data, Power Modules Feature Data Memory cards MMC (we recommend a card with Order No. 6SL3254-0AM00-0AA0). SD (Secure Digital Memory Card, we recommend the card with Order No. 6ES7954-8LB00-0AA0). SDHC (SD High Capacity) cannot be used. Operating temperature If the safety functions of the Control Unit are locked: 0 °C …...
  • Page 264 Technical data 10.3 Technical data, Power Modules Note The base load (100% power or current) of "Low Overlaod" is greater than the base load of "High Overload". To select the Power Module on the basis of duty cycles, we recommend the "SIZER" engineering software.
  • Page 265: Technical Data, Pm240

    Technical data 10.3 Technical data, Power Modules 10.3.1 Technical data, PM240 Note The given input currents are valid for operation without a line reactor for a line voltage of 400 V with Vk = 1 % referred to the rated power of the inverter. If a line reactor is used, the specified values are reduced by a few percent.
  • Page 266 Technical data 10.3 Technical data, Power Modules Power-dependent data, PM240 - IP20 Table 10- 1 PM240 frame size A, 3-ph. 380 V AC… 480 V, ± 10 % Order number Without filter 6SL3224-0BE13-7UA0 6SL3224-0BE15-5UA0 6SL3224-0BE17-5UA0 Values based on Low Overload ●...
  • Page 267 Technical data 10.3 Technical data, Power Modules Table 10- 3 PM240 frame size B, 3-ph. 380 V AC… 480 V, ± 10 % Order number with filter 6SL3224-0BE22-2AA0 6SL3224-0BE23-0AA0 6SL3224-0BE24-0AA0 without filter 6SL3224-0BE22-2UA0 6SL3224-0BE23-0UA0 6SL3224-0BE24-0UA0 Values based on Low Overload ●...
  • Page 268 Technical data 10.3 Technical data, Power Modules Table 10- 5 PM240 frame size D, 3-ph. 380 V AC… 480 V, ± 10 % Order number with filter 6SL3224-0BE31-5AA0 6SL3224-0BE31-8AA0 6SL3224-0BE32-2AA0 without filter 6SL3224-0BE31-5UA0 6SL3224-0BE31-8UA0 6SL3224-0BE32-2UA0 Values based on Low Overload ●...
  • Page 269 Technical data 10.3 Technical data, Power Modules Table 10- 7 PM240 frame size F, 3-ph. 380 V AC… 480 V, ± 10 % Order number with filter 6SL3224-0BE34-5AA0 6SL3224-0BE35-5AA0 6SL3224-0BE37-5AA0 without filter 6SL3224-0BE34-5UA0 6SL3224-0BE35-5UA0 6SL3224-0BE37-5UA0 Values based on Low Overload ●...
  • Page 270 Technical data 10.3 Technical data, Power Modules Table 10- 9 PM240 frame size GX, 3-ph. 380 V AC… 480 V, ± 10 % Order number Without filter 6SL3224-0BE41-3UA0 6SL3224-0BE41-6UA0 6SL3224-0BE42-0UA0 Values based on Low Overload ● LO power 160 kW 200 kW 250 kW ●...
  • Page 271: Technical Data, Pm240-2

    Technical data 10.3 Technical data, Power Modules 10.3.2 Technical data, PM240-2 Note The given input currents are valid for operation without a line reactor for a line voltage of 400 V with Vk = 1 % referred to the rated power of the inverter. If a line reactor is used, the specified values are reduced by a few percent.
  • Page 272 Technical data 10.3 Technical data, Power Modules Performance dependent data - PM240-2 Table 10- 10 Frame size A, 3-ph. 380 V … 480 V AC, ± 10 % - Part 1 Order number With filter 6SL3210-1PE11-8AL0 6SL3210-1PE12-3AL0 6SL3210-1PE13-2AL0 Without filter 6SL3210-1PE11-8UL0 6SL3210-1PE12-3UL0 6SL3210-1PE13-2UL0...
  • Page 273 Technical data 10.3 Technical data, Power Modules Table 10- 11 Frame size A, 3-ph. 380 V … 480 V AC, ± 10 % - Part 2 Order number with filter, IP20 6SL3210-1PE14-3AL0 6SL3210-1PE16-1AL0 without filter, IP20 6SL3210-1PE14-3UL0 6SL3210-1PE16-1UL0 6SL3210-1PE18-0UL0 with filter, PT 6SL3211-1PE16-1AL0 without filter, PT 6SL3210-1PE18-0UL0...
  • Page 274: Technical Data, Pm250

    Technical data 10.3 Technical data, Power Modules 10.3.3 Technical data, PM250 General data, PM250 - IP20 Feature Version Line voltage 3-ph. 380 V … 480 V AC ± 10 % The actual permissible line voltage depends on the installation altitude Input frequency 47 Hz …...
  • Page 275 Technical data 10.3 Technical data, Power Modules Power-dependent data, PM250 - IP20 Table 10- 12 PM250 frame size C, 3-ph. 380 V AC… 480 V, ± 10 % Order number 6SL3225-0BE25-5AA0 6SL3225-0BE27-5AA0 6SL3225-0BE31-1AA0 Values based on Low Overload ● LO power 7.5 kW 11.0 kW 15 kW...
  • Page 276 Technical data 10.3 Technical data, Power Modules Table 10- 14 PM250 frame size E, 3-ph. 380 V AC… 480 V, ± 10 % Order number 6SL3225-0BE33-0AA0 6SL3225-0BE33-7AA0 Values based on Low Overload ● LO power 37 kW 45 kW ● LO input current 70 A 84 A ●...
  • Page 277: Technical Data, Pm250-2

    Technical data 10.3 Technical data, Power Modules 10.3.4 Technical data, PM250-2 General data, PM250-2 Feature Specification Line voltage 3-ph. 380 V … 480 V AC ± 10 % The actual permissible line voltage depends on the installation altitude Input frequency 47 Hz …...
  • Page 278 Technical data 10.3 Technical data, Power Modules Performance dependent data, PM250-2 Table 10- 16 Frame sizes A, 3-ph. 380 V … 480 V AC, ± 10 % - Part 1 Order No. with filter, IP20 6SL3210-1QE11-8AL0 6SL3210-1QE12-3AL0 6SL3210-1QE13-2AL0 without filter, IP20 6SL3210-1QE11-8UL0 6SL3210-1QE12-3UL0 6SL3210-1QE13-2UL0...
  • Page 279 Technical data 10.3 Technical data, Power Modules Table 10- 17 Frame sizes A, 3-ph. 380 V … 480 V AC, ± 10 % - Part 2 Order No. with filter, IP20 6SL3210-1QE14-3AL0 6SL3210-1QE16-1AL0 6SL3210-1QE18-0AL0 without filter, IP20 6SL3210-1QE14-3UL0 6SL3210-1QE16-1UL0 6SL3210-1QE18-0UL0 with filter, PT 6SL3211-1QE18-0AL0 without filter, PT...
  • Page 280 Technical data 10.3 Technical data, Power Modules Table 10- 18 Frame sizes B, 3-ph. 380 V … 480 V AC, ± 10 % - Part 1 Order No. with filter, IP20 6SL3210-1QE21-0AL0 6SL3210-1QE21-3AL0 6SL3210-1QE21-8AL0 without filter, IP20 6SL3210-1QE21-0UL0 6SL3210-1QE21-3UL0 6SL3210-1QE21-8UL0 with filter, PT 6SL3211-1QE21-8AL0 without filter, PT...
  • Page 281: Technical Data, Pm260

    Technical data 10.3 Technical data, Power Modules 10.3.5 Technical data, PM260 General data, PM260 - IP20 Feature Version Line voltage 3-ph. 660 V … 690 V AC ± 10% The permissible line voltage depends on the installation altitude The power units can also be operated with a minimum voltage of 500 V –10 %. In this case, the power is linearly reduced as required.
  • Page 282 Technical data 10.3 Technical data, Power Modules Power-dependent data, PM260 - IP20 Table 10- 19 PM260 frame size D, 3-ph. 660 V AC… 690 V, ± 10% (500 V - 10%) Order number with filter 6SL3225- 0BH27-5AA1 6SL3225- 0BH31-1AA1 6SL3225- 0BH31-5AA1 without filter 6SL3225- 0BH27-5UA1 6SL3225- 0BH31-1UA1...
  • Page 283: Index

    Index BOP-2, 25 Display, 68 Menu, 69 Brake Relay, 197 87 Hz characteristic, 45 Braking Regenerative, 196 Braking chopper, 194 Braking method, 189 Acceptance test, 224 Braking resistor, 194 Authorized person, 224 Break loose torque, 19 Preconditions, 224 Bus fault, 244 reduced, 225, 240, 241 Bus termination, 51 Requirements, 224...
  • Page 284 Index Updating, 225 Control Units, 25 Electromagnetic interference, 46 Control word, 113 Electromechanical sensor, 214 Control word 1, 114 Elevator, 201 Control word 3, 115 Emergency stop control device, 214 Conveyor belt, 190 End customer, 226 Copy Energy recovery option, 179, 196 Series commissioning, 225 Expert list, 85 Copy parameters...
  • Page 285 Index Free, 210, 212 Function Manual for Safety Integrated, 13 JOG function, 165 Function table, 227 Function test STO, 227 Functional expansions, 225 functions KTY 84 temperature sensor, 63, 176 Technological, 156 Functions BOP-2, 69 Overview, 155 BF, 244 RDY, 244 SAFE, 245 Getting Started, 13 LED (light emitting diode), 243...
  • Page 286 Index Motor holding brake, 187, 198, 200, 201 PKW (parameter, ID, value), 112 Motor rating plate, 58 PLC functionality, 22 Motor temperature sensor, 52, 63, 64, 65, 66, 67, 177 PLC program, 229 Motorized potentiometer, 160 Power failure, 205 Multiple assignment Power Module, 25, 27 Digital inputs, 223 Technical data, 265, 271, 274, 277, 281...
  • Page 287 Index Sensor Power Module, 265, 271, 274, 277, 281 Electromechanical, 215 Technology controller, 115, 209 Serial number, 226 Telegram types, 109, 112 Series commissioning, 225 Temperature calculation, 178 Setpoint calculation, 166 Temperature measurement via KTY, 176 Setpoint processing, 156 Temperature measurement via PTC, 176 Setpoint source, 59, 156 Temperature monitoring, 175, 176, 178 Selecting, 159...
  • Page 288 Index Safety function, 226 Vertical conveyors, 169, 187, 194, 197 Voltage boost, 19, 172, 173 voltage input, 98 Voltage input Bipolar, 62 Voltage output, 63, 101 Winders, 169, 196 Wire break, 216 Wire-break monitoring, 177 ZSW (status word), 112 ZSW1 (status word 1), 116 ZSW3 (status word 3), 117 Inverter with CU240B-2 and CU240E-2 Control Units Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA...
  • Page 290 Siemens AG We reserve the right to make technical Industry Sector changes. Drive Technologies © Siemens AG 2010 Motion Control Systems Postfach 3180 91050 ERLANGEN GERMANY www.siemens.com/sinamics-g120...

This manual is also suitable for:

Sinamics g120 cu240e-2Sinamics g120 cu240b-2 dpSinamics g120 cu240e-2 dpSinamics g120 cu240e-2 fSinamics g120 cu240e-2 dp-f

Table of Contents