Removing functional grounding connections from the converter
Precondition
Switch off the converter power supply before removing the functional grounding.
Electric shock as a result of a residual charge in power components
After the power supply has been switched off, it takes up to five minutes until the capacitors
in the converter have discharged so that the residual charge is at a non-hazardous level.
Therefore, touching the converter immediately after powering off can result in electric
shock due to residual charge in the power components.
Procedure
1. Release the retaining screws (6 x M4) for the Electronic Module by using a 3 mm allen key,
and then remove the module.
2. Remove the functional grounding screw marked with the
the Electronic Module.
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
WARNING
Check the voltage at the converter connections before you remove the functional grounding.
Wiring
4.2 Permissible line supplies
symbol from the back side of
51