PID technology controller, fixed values (binary selection)
Parameter
p2201[0...n]
...
p2215[0...n]
p2216[0...n]
r2224
r2225.0
r2229
PID technology controller, fixed values (direct selection)
Parameter
p2216[0...n]
p2220[0...n]
...
p2223[0...n]
r2224
r2225.0
r2229
PID technology controller, motorized potentiometer
Parameter
r2231
p2235[0...n]
p2236[0...n]
p2237[0...n]
p2238[0...n]
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
Description
CO: Technology controller fixed
value 1 ... 15 [%]
Technology controller fixed value
selection method
CO: Technology controller fixed
value active [%]
CO/BO: Technology controller fixed
value selection status word [%]
Technology controller number
actual
Description
Technology controller fixed value
selection method
BI: Technology controller fixed
value selection bit 0 ... 3
CO: Technology controller fixed
value active [%]
CO/BO: Technology controller fixed
value selection status word [%]
Technology controller number
actual
Description
Technology controller motorized
potentiometer setpoint memory [%]
BI: Technology controller motor-
ized potentiometer, setpoint, raise
BI: Technology controller motor-
ized potentiometer, setpoint,
lower
Technology controller motorized
potentiometer maximum value
[%]
Technology controller motorized
potentiometer minimum value [%]
Advanced commissioning
6.17 PID technology controller
Setting
Sets the value for fixed value 1 ... 15 of the tech-
nology controller.
Factory setting: 10, 20, 30 ... 150
Sets the method to select the fixed setpoints:
1: Direct selection (factory setting)
2: Binary selection
Display and connector output for the selected and
active fixed value of the technology controller.
Display and BICO output for the status word of the fixed
value selection of the technology controller.
Displays the number of the selected fixed setpoint
of the technology controller.
Setting
Sets the method to select the fixed setpoints:
1: Direct selection (factory setting)
2: Binary selection
Sets the signal source to select a fixed value of
the technology controller.
Factory setting: 0
Display and connector output for the selected and
active fixed value of the technology controller.
Display and BICO output for the status word of the fixed
value selection of the technology controller.
Displays the number of the selected fixed setpoint
of the technology controller.
Setting
Displays the setpoint memory for the motorized
potentiometer of the technology controller.
Sets the signal source to continually increase the
setpoint for the motorized potentiometer of the
technology controller.
Factory setting: 0
Sets the signal source to continually reduce the
setpoint for the motorized potentiometer of the
technology controller.
Factory setting: 0
Sets the maximum value for the motorized poten-
tiometer of the technology controller.
Factory setting: 100
Sets the minimum value for the motorized poten-
tiometer of the technology controller.
Factory setting: -100