Technical data
10.2 Technical data of the G115D wall-mounted converter
Standby currents
G115D wall-mounted converter
Frame size
Rated power
FSA
0.37 kW to 1.5 kW
FSB
2.2 kW to 4 kW
FSC
5.5 kW to 7.5 kW
G115D wall-mounted converter
Frame size
Rated power
FSA
0.37 kW to 1.5 kW
FSB
2.2 kW to 4 kW
FSC
5.5 kW to 7.5 kW
10.2.4

Technical data of braking resistors

Technical data of integrated braking resistor
G115D wall-mounted converter
Frame size
FSA
FSB
FSC
Peak power at 10% cycle time of a 120s cycle.
1)
374
Standby current (mA)
Mains power supply without 24 V DC power supply
380 V, 50 Hz
380 V, 60 Hz
136
163
172
207
255
306
Standby current (mA)
Mains power supply with 24 V DC power supply
380 V, 50 Hz
380 V, 60 Hz
168
195
204
239
287
338
Rated power
Resistance
0.37 kW to 1.5 kW
350 Ω
2.2 kW to 4 kW
175 Ω
5.5 kW to 7.5 kW
88 Ω
400 V, 50 Hz
400 V, 60 Hz
143
171
181
217
268
322
400 V, 50 Hz
400 V, 60 Hz
171
199
209
246
296
350
Integrated braking resistor
Continuous braking power
10 W
10 W
20 W
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
480 V, 50 Hz
480 V, 60 Hz
171
206
217
261
321
386
480 V, 50 Hz
480 V, 60 Hz
189
224
235
279
339
404
Peak braking power
100 W
100 W
200 W