Alarms, faults and system messages
8.6 List of alarms and faults
Number
Cause
F30001
Overcurrent
F30002
DC-link voltage overvoltage
F30003
DC-link voltage undervoltage
F30004
Converter overtemperature
F30005
I2t converter overload
F30011
Line phase failure
F30015
Motor cable phase failure
F30021
Ground fault
F30022
Power Module: Monitoring U
F30027
Time monitoring for DC link pre-
charging
F30035
Overtemperature, intake air
F30036
Overtemperature, inside area
F30037
Rectifier overtemperature
F30052
Incorrect Power Module data
A30502
DC link overvoltage
F30662
CU hardware fault
F30664
CU power up aborted
F30850
Software fault in Power Module
A30920
Temperature sensor fault
For details, please refer to the List Manual.
336
Remedy
Check the following:
Motor data, if required, carry out commissioning
Motor connection method (Υ / Δ)
U/f operation: Assignment of rated currents of motor and Power Module
Line quality
Power cable connections
Power cables for short-circuit or ground fault
Power cable length
Line phases
If this doesn't help:
U/f operation: Increase the acceleration ramp
Reduce the load
Replace the power unit
Increase the ramp-down time (p1121).
Set the rounding times (p1130, p1136).
Activate the DC link voltage controller (p1240, p1280).
Check the line voltage (p0210).
Check the line phases.
Check the line voltage (p0210).
Check whether the converter fan is running.
Check whether the ambient temperature is in the permissible range.
Check whether the motor is overloaded.
Reduce the pulse frequency.
Check the rated currents of the motor and Power Module.
Reduce current limit p0640.
When operating with U/f characteristic: Reduce p1341.
Check the converter's input fuses.
Check the line cables.
Check the motor cables.
Increase the ramp-up or ramp-down time (p1120).
Check the power cable connections.
Check the motor.
Check the current transformer.
Check the cables and contacts of the brake connection (a wire might
be broken).
Check or replace the Power Module.
CE
Check the supply voltage at the input terminals.
Check the line voltage setting (p0210).
Check whether the fan is running.
Check the fan filter elements.
Check whether the ambient temperature is in the permissible range.
See F30035 and, in addition:
Check the motor load.
Check the line phases
Replace Power Module or upgrade CU firmware.
Check the unit supply voltage (p0210).
Switch CU off and on again, upgrade firmware, or contact technical support.
Switch CU off and on again, upgrade firmware, or contact technical support.
Replace Power Module or contact technical support.
Check that the sensor is connected correctly.