Parameters
Basic settings
Parameter
p1215
p1216
p1217
r0052.12
Advanced settings
Parameter
p0346
p0855
p0858
p1226
p1227
p1228
p1351
p1352
p1475
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
Description
Enable motor holding
brake
Motor holding brake
opening time [s]
Motor holding brake
closing time [s]
CO/BO: Status word 1:
motor holding brake open
Description
Motor excitation build-
up time [s]
BI: Unconditionally re-
lease holding brake
BI: Unconditionally close
holding brake
Threshold for zero speed
detection [rpm]
Zero speed detection
monitoring time [s]
Pulse suppression delay
time [s]
CO: Motor holding brake
starting frequency [%]
CI: Motor holding brake
starting frequency signal
source
CI: Speed controller
torque setting value for
motor holding brake
Setting
0: Motor holding brake locked (factory setting)
1: Motor holding brake just like the sequence control
2: Motor holding brake permanently open
3: Motor holding brake just like the sequential control, con-
nected via BICO
p1216 > braking signal relay runtimes + brake release time
Factory setting: 0.1
p1217 > braking signal relay runtimes + brake closing time
Factory setting: 0.1
-
Setting
During this time the asynchronous motor is magnetized. The
converter calculates this parameter using p0340 = 1 or 3.
Factory setting: 0
Sets the signal source for the command "unconditionally
open holding brake".
Factory setting: 0
Sets the signal source for the command "unconditionally
close holding brake".
Factory setting: 0
When braking with OFF1 or OFF3, if the speed falls below
this threshold, standstill is detected and the monitoring time
p1227 or p1228 starts.
Factory setting: 20
Sets the monitoring time for the standstill identification.
Factory setting: 300
Sets the delay time for pulse suppression.
Factory setting: 0.01
Sets the frequency set value at the slip compensation output
when starting with motor holding brake.
With p1351 > 0, slip compensation is automatically switched
on.
Factory setting: 0
Sets the signal source for the frequency set value at the slip
compensation output when starting with motor holding
brake.
Factory setting: 1351
Sets the signal source for the torque set value when starting
with motor holding brake.
Factory setting: 0
Advanced commissioning
6.11 Motor holding brake