Telegram
Set the same telegram in the converter as in the IO Controller. Interconnect the telegrams in
the control program of the IO Controller with the signals of your choosing.
Application examples
You can find application examples for PROFINET communication on the Internet:
PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI
(https://support.industry.siemens.com/cs/ww/en/view/60441457)
PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI
(https://support.industry.siemens.com/cs/ww/en/view/78788716)
4.13.6

Installing GSDML

Procedure
1. Save the GSDML to your PC.
– With Internet access:
– Without Internet access:
2. Unzip the GSDML file on your computer.
3. Import the GSDML into the engineering system of the controller.
You have now installed the GSDML in the engineering system of the controller.
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
Drive control via PROFINET (Page 134)
Controlling the speed of a SINAMICS G110M/G120/G120C/G120D with S7-300/400F via
Controlling the speed of a SINAMICS G110M/G120 (Startdrive) with S7-1500 (TO) via
GSDML (https://support.industry.siemens.com/cs/ww/en/view/26641490)
Insert a memory card into the converter.
Set p0804 = 12.
The converter writes the GSDML as zipped file (*.zip) into directory
/SIEMENS/SINAMICS/DATA/CFG on the memory card.
4.13 Connecting to PROFINET and Ethernet
Wiring
87