Procedure with Startdrive when the safety functions are enabled
1. Save the project.
2. Select the
3. Connect Startdrive online with the drive.
4. Press the
5. Enter the password for the safety functions.
If the password is the factory default, you are prompted to change the password.
If you try to set a password that is not permissible, the old password will not be changed.
6. Press the
7. Confirm the prompt for saving your settings (copy RAM to ROM).
8. Disconnect the online connection.
9. Switch off the converter power supply.
10.Wait until all LEDs on the converter go dark (no voltage condition).
11.Switch on the converter power supply again.
You have transferred the settings from the PG/PC to the converter with Startdrive and have
activated the safety functions.
❒
7.3
Other ways to back up settings
In addition to the default setting, the converter has an internal memory for backing up three
other settings.
On the memory card, you can back up 99 other settings in addition to the default setting.
Additional information is available on the Internet: Memory options
(http://support.automation.siemens.com/WW/view/en/43512514)
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
button to transfer settings from the PG/PC to the converter.
button to start the safety commissioning.
button to end the safety commissioning.
Data backup and series commissioning
7.3 Other ways to back up settings
289