Delta ASDA-B2-F Series User Manual page 168

Economic ac servo drive with dmcnet communication
Table of Contents

Advertisement

ASDA-B2-F
6: 8, N, 2(MODBUS, RTU)
P3-03
Operational
Panel / Software Communication
Interface:
Default: 0
Unit: -
Format: HEX
Settings:
The definition of the setting value is as the followings:
0: Warning displays and motor keeps running
1: Warning displays and motor decelerates to stop (The deceleration time can be set via P5-03.B)
P3-04
Operational
Panel / Software Communication
Interface:
Default: 0
Unit: sec
Format: DEC
Settings:
If the setting value is not 0, the communication timeout function is enabled immediately. If it is set to
0, this function will be disabled.
P3-05
Operational
Panel / Software Communication
Interface:
Default: 0
Unit: -
Format: HEX
Settings:
Communication interface selection (one or more than one communication)
Communication Interface: 0: RS-232
P3-06■
Operational
Panel / Software Communication
Interface:
Default: 0
Unit: -
Format: HEX
Settings:
Control switch of DI source. Each bit of this parameter decides one input source of DI signal:
Bit0 ~ Bit4 correspond to DI1 ~ DI5.
The setting of bit is as the followings:
0: The input status is controlled by the external hardware terminal.
1: The input status is controlled by P4-07.
For functional planning of digital input, please refer to:
DI1 ~ DI5: P2-10 ~ P2-14
September, 2015
7: 8, E, 1(MODBUS, RTU)
FLT
Communication Error Disposal
CWD
Communication Timeout
CMM
Communication Mechanism
SDI
Control Switch of Digital Input (DI)
8: 8, O, 1(MODBUS, RUT)
Address: 0306H
Related
-
Section:
Control
ALL
Mode:
Range: 0 ~ 1
Data Size: 16-bit
Address: 0308H
Related
-
Section:
Control
ALL
Mode:
Range: 0 ~ 20
Data Size: 16-bit
Address: 030AH
Related
-
Section:
Control
ALL
Mode:
Range: 0x00 ~ 0x01
Data Size: 16-bit
Address: 030CH
Related
-
Section:
Control
ALL
Mode:
Range: 0x0000 ~ 0x3FFF
Data Size: 16-bit
Parameters
0307H
7
0309H
030BH
030DH
7-51