u Network Termination
The two ends of the MEMOBUS/Modbus network line have to be terminated. The drive has a built in termination
resistor that can be enabled or disabled using DIP switch S1. If a drive is located at the end of a network line, enable the
termination resistor by setting DIP switch S1 to the ON position. Disable the termination resistor on all slaves that are not
located at the network line end.
Figure C.3
illustrates the setting of DIP switch S1.
To set the DIP switch on the terminal board, use an appropriate sized tool with a tip of approximately 8 mm in width.
Figure C.3
<Position of the controller>
Drive panel
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
<Status with the controller drawn out>
Controller
(Draw-out
construction)
DIP switch S1
OFF
ON
(OFF: default)
Figure C.3 Serial Communications Terminal and DIP Switch S1
C.3 Connecting to a Network
Controller
RS-485
Termination resistor (1/2 W, 120 Ω)
Asia
S -
-
S+
+
R -
DIP
switch
R+
S1
C
227