B.10 o: Operator-Related Settings
u

o3: Copy Function

No.
(Addr.
Name
Hex)
o3-01
Copy Function Selection
(515)
o3-02
Copy Allowed Selection
(516)
u

o4: Maintenance Monitor Settings

No.
(Addr.
Name
Hex)
o4-01
Cumulative Operation
(50B)
Time Setting
o4-02
Cumulative Operation
(50C)
Time Selection
o4-03
Cooling Fan Operation
(50E)
Time Setting
o4-05
Capacitor Maintenance
(51D)
Setting
DC Bus Pre-Charge
o4-07
Relay Maintenance
(523)
Setting
o4-11
U2, U3 Initialization
(510)
o4-12
kWh Monitor
(512)
Initialization
Number of Run
o4-13
Commands Counter
(528)
Initialization
o4-17
Set/Reset Real Time
(3100)
Clock
308
LCD Display
0: No action
COPY SELECT
1: Read parameters from the drive, saving them onto the HOA
0: COPY SELECT
keypad.
1: INV→OP READ
2: Copy parameters from the HOA keypad, writing them to the
2: OP→INV WRITE
drive.
3: OP←→INV
3: Verify parameter settings on the drive to check if they match
VERIFY
the data saved on the HOA keypad.
Read Allowable
0: Read operation prohibited
0: Disabled
1: Read operation allowed
1: Enabled
LCD Display
Sets the value for the cumulative operation time of the drive in
DrvElapsTimeCnt
units of 10 h.
ElapsTimeCntSet
0: Logs power-on time
0: Power-On Time
1: Logs operation time when the drive output is active (output
1: Running Time
operation time).
Sets the value of the fan operation time monitor U4-03 in units
FanElapsTimeCn
of 10 h.
Sets the value of the Maintenance Monitor for the capacitors. See
BusCap Maint Set
U4-05 to check when the capacitors may need to be replaced.
Sets the value of the Maintenance Monitor for the soft charge
ChrgCircMaintSet
bypass relay. See U4-06 to check when the bypass relay may need
to be replaced.
0: U2-oo and U3-oo monitor data is not reset when the drive
Fault Data Init
is initialized (A1-03).
0: No Reset
1: U2-oo and U3-oo monitor data is reset when the drive is
1: Reset
initialized (A1-03).
0: U4-10 and U4-11 monitor data is not reset when the drive is
kWh Monitor Init
initialized (A1-03).
0: No Reset
1: U4-10 and U4-11 monitor data is reset when the drive is
1: Reset
initialized (A1-03).
0: Number of Run commands counter is not reset when the drive
Run Counter Init
is initialized (A1-03).
0: No Reset
1: Number of Run commands counter is reset when the drive is
1: Reset
initialized (A1-03).
Set Time
Sets the current date and time for the Real Time Clock.
0: — —
0: — — No Setting
1: Set
1: Real Time Clock Set
2: Reset
2: Real Time Clock Reset
Description
Description
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Values
Page
Default: 0
185
Range: 0 to 3
Default: 0
185
Range: 0, 1
Values
Page
Default: 0 h
Min.: 0
185
Max.: 9999
Default: 1
185
Range: 0, 1
Default: 0 h
Min.: 0
186
Max.: 9999
Default: 0%
Min.: 0
186
Max.: 150
Default: 0%
Min.: 0
186
Max.: 150
Default: 0
186
Range: 0, 1
Default: 0
186
Range: 0, 1
Default: 0
186
Range: 0, 1
Default: 0
186
Range: 0 to 2