C6: Carrier Frequency

No.
(Addr.
Name
Hex)
C6-02
Carrier Frequency
(224)
Selection
C6-03
Carrier Frequency
(225)
Upper Limit
C6-04
Carrier Frequency
(226)
Lower Limit
C6-05
Carrier Frequency
(227)
Proportional Gain
<1> Default setting value is dependent on parameters A1-02, Control Method Selection and o2-04, Drive Model Selection.
<2> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection.
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
LCD Display
CarrierFreq Sel
1: 2.0 kHz
1: 2.0 kHz
2: 5.0 kHz
2: 5.0 kHz
3: 8.0 kHz
3: 8.0 kHz
4: 10.0 kHz
4: 10.0 kHz
5: 12.5 kHz
5: 12.5 kHz
7: Swing PWM1 (Audible sound 1)
7: Swing PWM1
8: Swing PWM2 (Audible sound 2)
8: Swing PWM2
9: Swing PWM3 (Audible sound 3)
9: Swing PWM3
A: Swing PWM4 (Audible sound 4)
A: Swing PWM4
B to E: No setting possible
F: Program
F: User-defined (determined by C6-03 through C6-05)
Determines the upper and lower limits for the carrier frequency.
CarrierFreq Max
CarrierFreq Min
CarrierFreq Gain
Description
Carrier Frequency
C6-03
C6-04
Output Frequency
× (C6-05) × K
E1-04
Max Output
Frequency
B.3 C: Tuning
Values
<1>
Default:
Range: 1 to 5; 7 to
9; A, F
<2>
Default:
Min.: 1.0 kHz
Max.: 12.5 kHz
<2>
Default:
Min.: 1.0 kHz
Max.: 12.5 kHz
Output
<2>
Default:
Frequency
Min.: 0
Max.: 99