B2: Dc Injection Braking And Short Circuit Braking; B3: Speed Search - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

11.5 b: Application
No.
Name
(Hex.)
b1-16
Run Command Selection
2
(01C5)
b1-17
Run Command at Power
Up
(01C6)
b1-35
Digital Input Deadband
Time
(1117)
Expert

b2: DC Injection Braking and Short Circuit Braking

No.
Name
(Hex.)
b2-01
DC Injection/Zero
SpeedThreshold
(0189)
b2-02
DC Injection Braking
Current
(018A)
b2-03
DC Inject Braking Time
at Start
(018B)
b2-04
DC Inject Braking Time
at Stop
(018C)
b2-08
Magnetic Flux
Compensation Value
(0190)
b2-12
Short Circuit Brake Time
@ Start
(01BA)
b2-13
Short Circuit Brake Time
@ Stop
(01BB)
b2-18
Short Circuit Braking
Current
(0177)

b3: Speed Search

No.
Name
(Hex.)
b3-01
Speed Search at Start
Selection
(0191)
b3-02
SpeedSearch
Deactivation Current
(0192)
340
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the input method for Run Command 2 when the user switches the control circuit
terminals ON/OFF to change the Run command source.
0 : Keypad
1 : Digital Input
2 : Memobus/Modbus Communications
3 : Option PCB
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets drive response when energizing a drive that has an external Run command. Set this
parameter in applications where energizing or de-energizing the drive enables the Run
command.
0 : Disregard Existing RUN Command
1 : Accept Existing RUN Command
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the deadband time for MFDIs.
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency to start DC Injection Braking or Short Circuit Braking.
Note:
This parameter is available when b1-03 = 0 [Stopping Method Selection = Ramp to
Stop].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the DC Injection Braking current as a percentage of the drive rated current.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the DC Injection Braking Time at stop.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the DC Injection Braking Time at stop.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets how much current the drive injects when DC Injection Braking at Start starts
(Initial Excitation) as a percentage of E2-03 [Motor No-Load Current].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the Short Circuit Braking time at start.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the Short Circuit Braking time at stop.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Short Circuit Braking Current as a percentage of the motor rated current.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor
rated current.
• A1-02 = 5, 6 [OLV/PM, AOLV/PM]: E5-03 [PM Motor Rated Current (FLA)]
• A1-02 = 8 [EZOLV]: E9-06 [Motor Rated Current (FLA)]
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Speed Search at Start function where the drive will perform Speed Search with
each Run command.
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the current level that stops Speed Search as a percentage of the drive rated output
current. Usually it is not necessary to change this setting.
Default
(Setting Range)
0
(0 - 3)
0
(0, 1)
0.0 ms
(0.0 to 100.0 ms)
Default
(Range)
Determined by A1-02
(0.0 - 10.0 Hz)
50%
(0 - 75%)
0.00 s
(0.00 - 10.00 s)
Determined by A1-02
(0.00 - 10.00 s)
0%
(0 - 1000%)
0.00 s
(0.00 - 25.50 s)
A1-02 = 8: 0.00 s
Other than A1-02 = 8:
0.50 s
(0.00 - 25.50 s)
100.0%
(0.0 - 200.0%)
Default
(Range)
Determined by A1-02
(0, 1)
Determined by A1-02
(0 - 200%)
YASKAWA SIEPC71061753A GA500 Technical Manual
Ref.
485
486
486
Ref.
486
487
487
487
488
488
488
489
Ref.
492
492

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents