11.5 b: Application
No.
Name
(Hex.)
b1-16
Run Command Selection
2
(01C5)
b1-17
Run Command at Power
Up
(01C6)
b1-35
Digital Input Deadband
Time
(1117)
Expert
◆
b2: DC Injection Braking and Short Circuit Braking
No.
Name
(Hex.)
b2-01
DC Injection/Zero
SpeedThreshold
(0189)
b2-02
DC Injection Braking
Current
(018A)
b2-03
DC Inject Braking Time
at Start
(018B)
b2-04
DC Inject Braking Time
at Stop
(018C)
b2-08
Magnetic Flux
Compensation Value
(0190)
b2-12
Short Circuit Brake Time
@ Start
(01BA)
b2-13
Short Circuit Brake Time
@ Stop
(01BB)
b2-18
Short Circuit Braking
Current
(0177)
◆
b3: Speed Search
No.
Name
(Hex.)
b3-01
Speed Search at Start
Selection
(0191)
b3-02
SpeedSearch
Deactivation Current
(0192)
340
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the input method for Run Command 2 when the user switches the control circuit
terminals ON/OFF to change the Run command source.
0 : Keypad
1 : Digital Input
2 : Memobus/Modbus Communications
3 : Option PCB
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets drive response when energizing a drive that has an external Run command. Set this
parameter in applications where energizing or de-energizing the drive enables the Run
command.
0 : Disregard Existing RUN Command
1 : Accept Existing RUN Command
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the deadband time for MFDIs.
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency to start DC Injection Braking or Short Circuit Braking.
Note:
This parameter is available when b1-03 = 0 [Stopping Method Selection = Ramp to
Stop].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the DC Injection Braking current as a percentage of the drive rated current.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the DC Injection Braking Time at stop.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the DC Injection Braking Time at stop.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets how much current the drive injects when DC Injection Braking at Start starts
(Initial Excitation) as a percentage of E2-03 [Motor No-Load Current].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the Short Circuit Braking time at start.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the Short Circuit Braking time at stop.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Short Circuit Braking Current as a percentage of the motor rated current.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor
rated current.
• A1-02 = 5, 6 [OLV/PM, AOLV/PM]: E5-03 [PM Motor Rated Current (FLA)]
• A1-02 = 8 [EZOLV]: E9-06 [Motor Rated Current (FLA)]
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Speed Search at Start function where the drive will perform Speed Search with
each Run command.
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the current level that stops Speed Search as a percentage of the drive rated output
current. Usually it is not necessary to change this setting.
Default
(Setting Range)
0
(0 - 3)
0
(0, 1)
0.0 ms
(0.0 to 100.0 ms)
Default
(Range)
Determined by A1-02
(0.0 - 10.0 Hz)
50%
(0 - 75%)
0.00 s
(0.00 - 10.00 s)
Determined by A1-02
(0.00 - 10.00 s)
0%
(0 - 1000%)
0.00 s
(0.00 - 25.50 s)
A1-02 = 8: 0.00 s
Other than A1-02 = 8:
0.50 s
(0.00 - 25.50 s)
100.0%
(0.0 - 200.0%)
Default
(Range)
Determined by A1-02
(0, 1)
Determined by A1-02
(0 - 200%)
YASKAWA SIEPC71061753A GA500 Technical Manual
Ref.
485
486
486
Ref.
486
487
487
487
488
488
488
489
Ref.
492
492