Goodrive300 Series VFD
Function
code
P06.05
P06.06
Y switch-on delay time
P06.07
Y switch-off delay time
P06.08
HDO switch-on delay time
P06.09
HDO switch-off delay time
P06.10
RO1 switch-on delay time 0.000–50.000s
P06.11
RO1 switch-off delay time 0.000–50.000s
P06.12
RO2 switch-on delay time 0.000–50.000s
P06.13
RO2 switch-off delay time 0.000–50.000s
Output terminals state at
P07.40
Digital output terminals
P17.13
7.13 Simple PLC
Simple PLC function is also a multi-step speed generator. The VFD can change the running frequency,
direction to meet the need of processing according to the running time automatically. In the past, this
function needs to be assisted by external PLC, but now the VFD can realize this function by itself.
The series VFDs can control 16-stage speed with 4 groups of ACC/DEC time.
The multi-function digital output terminals or multi-function relay output an ON signal when the set
PLC finishes a circle (or a stage).
P10.00(simple PLC)
Stop after running
0
one time
1
Run at the final value
after running for one
time
2
Cycle
PLC method
Name
Polarity of output
terminals
current fault
state
Power off during running
Running
parameter setting
in all stages in
PLC
Detailed instruction of parameters
25:
Ethernet
communication
terminals output
26: Voltage establishment finished
27–30: Reserved
0x00–0x0F
0.000–50.000s
0.000–50.000s
0.000–50.000s
(valid only when P06.00=1)
0.000–50.000s
(valid only when P06.00=1)
P10.01 (simple PLC memory selection)
0
Power off without memory
1
Power off with
memory
Normal running
P10.36
(PLC starting selection)
173
Basic operation instruction
virtual
0
Restart from
the first stage
0
1
Restart form the
1
frequency of the
pause stage
Terminal function 23
Simple PLC stop reset
Default
value
0x00
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0
0
Set frequency
P17.00