Goodrive300 Series VFD
Function
Name
code
Switch-on
P05.14
delay of S1
terminal
Switch-off
P05.15
delay of S1
terminal
Switch-on
P05.16
delay of S2
terminal
Switch-off
P05.17
delay of S2
terminal
Switch-on
P05.18
delay of S3
terminal
Detailed instruction of parameters
Sln
FWD
ON
OFF→ON
ON
ON
OFF
ON→OFF
SIn: 3-wire operation control; FWD: Forward
running; REV: Reverse running
Note: For the 2-wire running mode, when the
FWD/REV terminal is valid, and the VFD stops
because of the stop command from other
sources, the VFD won't work when the stopping
command is canceled even the control terminal
FWD/REV is still valid;. Only when FWD/REV is
re-triggered, the VFD can start again. For
example, the PLC single-cycle stop command,
fixed-period stop command, and the STOP/RST
stop command that is valid in terminal control
mode (see P07.04).
The function code defines the corresponding
delay time of electrical level of the programmable
terminals during switching on and switching off.
Si electrical level
Invalid
Si valid
Switcn-on
delay
Setting range: 0.000–50.000s
74
REV
Direction
ON
Forward
OFF
Reverse
Forward
OFF→ON
Reverse
Decelerate
to stop
Invalid
Valid
Switcn-off
delay
Function parameters
Default
Modify
value
0.000s
○
0.000s
○
0.000s
○
0.000s
○
0.000s
○