Goodrive300 Series VFD
Function parameters
Function
Default
Name
Detailed instruction of parameters
Modify
code
value
5: Simple PLC program setting
The VFD runs at simple PLC program mode
when P00.06=5 or P00.07=5. Set P10 (simple
PLC and multi-step speed control) to select the
running frequency, running direction, ACC/DEC
time and the keeping time of corresponding
stage. See the function description of P10 for
detailed information.
6: Multi-step speed running
The VFD runs at multi-step speed mode when
P00.06=6 or P00.07=6. Set P05 to select the
current running stage, and set P10 to select the
current running frequency.
The multi-step speed has the priority when
P00.06 or P00.07 does not equal to 6, but the
setting stage can only be the 1–15 stage. The
setting stage is 1–15 if P00.06 or P00.07 equals
to 6.
7: PID control setting
The running mode of the VFD is process PID
control when P00.06=7 or P00.07=7. It is
necessary to set P09. The running frequency of
the VFD is the value after PID effect. See P09 for
the detailed information of the given source, given
value, feedback source of PID.
8: Modbus communication setting
The frequency is set by Modbus communication.
See P14 for detailed information.
9: PROFIBUS/CANopen communication setting
The frequency is set by PROFIBUS/ CANopen
communication.
See P15 for the
detailed
information.
10: Ethernet communication setting(reserved)
11: Reserved
0: Max. output frequency, 100% of
B frequency
B frequency setting
corresponds to the
P00.08
command
0
maximum output frequency
reference
1: A frequency command, 100% of B frequency
44