INVT Goodrive300 Series Operation Manual page 150

Vfd
Table of Contents

Advertisement

Goodrive300 Series VFD
Function
code
Leakage inductance of
P02.08
asynchronous motor 1
Mutual inductance of
P02.09
asynchronous motor 1
P02.10
asynchronous motor 1
P02.15
synchronous motor 1
P02.16
synchronous motor 1
Number of poles pairs for
P02.17
synchronous motor 1
P02.18
synchronous motor 1
P02.19
synchronous motor 1
P02.20
synchronous motor 1
Direct axis inductance of
P02.21
synchronous motor 1
P02.22
synchronous motor 1
P02.23
Back EMF constant of
synchronous motor 1
Multi-function digital input
P05.01–P05
.09
(S1–S8, HDI) function
P08.31
Name
Non-load current of
Rated power of
Rated frequency of
Rated voltage of
Rated current of
Stator resistor of
Quadrature axis
inductance of
terminals
selection
Motor shifting
Detailed instruction of parameters
0.1–6553.5mH
0.1–6553.5mH
0.1–6553.5A
0.1–3000.0kW
0.01Hz–P00.03 (Max. frequency)
1–50
0–1200V
0.8–6000.0A
0.001–65.535Ω
0.01–655.35mH
0.01–655.35mH
0–10000
35: Shift from motor 1 to motor 2
LED ones: shifting channel
0: terminal shifting
1: Modbus communication shifting
2: PROFIBUS/CANopen communication
shifting
3: Ethernet communication shifting
4: Reserved
LED tens: shifting enabling in operation
145
Basic operation instruction
Default
value
Depend
on model
Depend
on model
Depend
on model
Depend
on model
50.00Hz
2
Depend
on model
Depend
on model
Depend
on model
Depend
on model
Depend
on model
300
00

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive300 Series and is the answer not in the manual?

Questions and answers